beautypg.com

Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 298

background image

Chapter

7


7-63 ADAM 4000 Series User’s Manual

@AAGN

Name

Read Initial Count Value of Counter 0 or 1 command

Description

Read the initial count value of counter 0 or 1 of the
specified counter module at address AA.

Syntax

@AAGN(data)(cr)

@

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the module.

GN

is the Read Initial Count Value for Counter 0 or 1

command.

N = 0 represents counter 0

N = 1 represents counter 1

(cr)

is the terminating character, carriage return (0Dh).

Response

!AA(data)(cr)

if the command is valid.

There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.

!

is a delimiter character which indicates a valid command.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the module.

(data)

is the initial count value which must consist of eight

hexadecimal digits.

(cr)

is the terminating character, carriage return (0Dh).

Example command:

@12G0(cr)

response: !12000000FF(cr)

The command instructs the module at address 12h to return
the initial value of counter 0. The module replies that
initial count value of counter 0 is 000000FF.

4080