Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 157

Chapter
5
5-11
ADAM 4000 Series User’s Manual
4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+
$AAF
Name
Read Firmware Version command
Description
The command requests the analog input module at address
AA to return the version code of its firmware.
Syntax
$AAF (cr)
$
is a delimiter character.
AA
(range 00-FF) represents the 2-character hexadecimal
address of the analog input module that you want to
interrogate.
F
is the Read Firmware Version command.
(cr)
is the terminating character, carriage return (ODh).
Response
!AA(Version)(cr)
if the command is valid.
There is no response if the module detects a syntax error or
communication error, or if the specified address does not
exist.
!
is a delimiter character indicating a valid command was
received.
AA
(range 00-FF) represents the 2-character hexadecimal
address of an analog input module.
(Version)
is the version code of the module’s firmware at
address AA.
(cr)
is the terminating character, carriage return (ODh).