Chapter

5


5-23

ADAM 4000 Series User’s Manual

4011D, 4015, 4015T, 4018+, 4019+

$AAB

Name

Channel Diagnose command

Description

Diagnose channel status in over range, under range, and
wire opening.

Syntax

$AAB(cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the analog input module to be detected.

B

is the Channel Diagnose command.

(cr)

is the terminating character, carriage return (0Dh).

Response

ADAM-4011D:

!AA0(cr)

if the module detects a close thermocouple.

!AA1(cr)

if the module detects an open thermocouple.

?AA(cr)

if an invalid command was issued.

ADAM-4015/4015T/4018+/4019+:

!AANN(cr)

if the command is valid when it applied with.

?AA(cr)

if an invalid command was issued.

There is no response if the module detects a syntax error or
communication error of if the specified address does not
exist.

!

delimiter character indicates a valid command was

received.

?

delimiter character indicates the command was invalid.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the analog input module.

NN

(range 00-FF) is a hexadecimal number that equals the

8-bit parameter, representing the status of analog input
channels. Bit value 0 means normal status; and bit value 1
means channel over range, under range, or open wiring.

(cr)

is the terminating character, carriage return (0Dh)