Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 169

Chapter
5
5-23
ADAM 4000 Series User’s Manual
4011D, 4015, 4015T, 4018+, 4019+
$AAB
Name
Channel Diagnose command
Description
Diagnose channel status in over range, under range, and
wire opening.
Syntax
$AAB(cr)
$
is a delimiter character.
AA
(range 00-FF) represents the 2-character hexadecimal
address of the analog input module to be detected.
B
is the Channel Diagnose command.
(cr)
is the terminating character, carriage return (0Dh).
Response
ADAM-4011D:
!AA0(cr)
if the module detects a close thermocouple.
!AA1(cr)
if the module detects an open thermocouple.
?AA(cr)
if an invalid command was issued.
ADAM-4015/4015T/4018+/4019+:
!AANN(cr)
if the command is valid when it applied with.
?AA(cr)
if an invalid command was issued.
There is no response if the module detects a syntax error or
communication error of if the specified address does not
exist.
!
delimiter character indicates a valid command was
received.
?
delimiter character indicates the command was invalid.
AA
(range 00-FF) represents the 2-character hexadecimal
address of the analog input module.
NN
(range 00-FF) is a hexadecimal number that equals the
8-bit parameter, representing the status of analog input
channels. Bit value 0 means normal status; and bit value 1
means channel over range, under range, or open wiring.
(cr)
is the terminating character, carriage return (0Dh)