$AA0

Name Span

Calibration

command

Description

Calibrates an analog input module to correct for gain errors.

Syntax

$AA0(cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the analog input module which is to be
calibrated.

0

is the Span Calibration command.

(cr)

is the terminating character, carriage return (0Dh).

Response

!AA(cr)

if the command was valid.

?AA(cr)

if an invalid operation was entered.

There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.

!

delimiter character indicates a valid command was

received.

?

delimiter character indicates the command was invalid.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the analog input module.

(cr)

represents terminating character, carriage return (0Dh).

In order to successfully calibrate an analog input module’s
input range, a proper calibration input signal should be
connected to the analog input module before and during the
calibration. (See also Chapter 8, Calibration)

NOTICE: An analog input module requires a maximum of 7 seconds to

perform auto calibration and ranging after it received a Span
Calibration command. During this interval, the module can not
be addressed to perform any other actions.