Rectifiers, Table 25 rectifiers configuration – GE Industrial Solutions Pulsar Plus Controller User Manual
Page 81

Pulsar Plus Controller Family
Issue 7 December 2011
81
Table 24 Shunt Type Configuration
Shunt
Type
System Configuration
Controller Operation
Shunt input may or may not be 
connected to a shunt located in the 
system. System has Shunt Monitors 
configured in the system and all system 
loads are monitored. 
 
And 
 
The new “All Load Monitored” feature 
has been “Enabled”. 
1. Cards configured to monitor “Battery”
shunts are assumed to monitor all battery 
current to and from the system batteries 
and are summed to the total battery 
current ( I
battery
). In addition, all individual
battery monitor values are displayed
2. Cards configured as monitoring a “Load”
shunt are summed to calculate the total 
I
Load
and also have their individual values
displayed.
Thus, the controller reports the following:
I
battery
= Σ I
battery shunt monitors
I
Load
= Σ I
Load shunt monitors
Note: If there are no Battery Shunt Monitors 
configured but the total load monitored is 
enabled, then the total battery current is 
calculated as follows: 
I
battery
= Unavailable
I
Load
= Σ I
Load shunt monitors
Recharge current feature is unavailable. 
 
Rectifiers
Table 25 Rectifiers Configuration
Redundancy
An alarm is automatically generated when the rectifier capacity On-line in the 
system falls below N+X based on the present system load. X is the desired 
number of rectifiers to check for redundancy. 
 
The factory default for this feature is Enabled and X=1. 
Rectifier On 
Threshold 
The system DC bus threshold that rectifiers placed into Standby will 
automatically be turned on. 
 
This value can be set between -40.00V and -51.00V and +20.00V to +25.00V 
with factory defaults set to -44.0V and +22.00V for 48V and 24V rectifiers, 
respectively. 
Remote Off
Provides the ability to disable or enable the capability of placing a rectifier into 
Standby operation through remote means such as the network, modem, or 
local terminal. 
 
The factory default for this feature is Disabled. 
Sequencing
When enabled, provides the ability to hold off a user configured group of 
rectifiers when appropriate contact closure is received, The feature is also 
called Group Standby. 
 
The factory default for this feature is Disabled. 
Current Limit
Adjustable from 30-100%. At 100% the rectifier will output its nameplate rating