Table d-1 standard configuration item defaults – GE Industrial Solutions Pulsar Plus Controller User Manual
Page 177

Pulsar Plus Controller Family
Issue 7 December 2011
177
Table D-1 Standard Configuration Item Defaults
Factory Default
Factory 24V
Rectifier
Default
Factory 48V
Rectifier
Default
Category
Description
Range
Factory
Factory 24V
Factory 48V
obj,attr
Battery 25 Type
"TEL12-105F"
BT25,BTY
Battery 25 Class
"VALVE-REG"
BT25,BTC
Battery 25 Capacity
100
BT25,CAP
Batteries
Number Of Battery Strings
0 to 16 Strings
0
DC1,NST
Battery Model
≤ 14 Characters
"Valve-Reg"
DC1,BTY
Battery
Discharge Test
Timed Test Duration
0:0:0 to 23:59:59
4:00:00
BR1,TMD
Automatic Battery Test Feature
disabled, 20%, timed
"disabled"
BR1,BTE
Automatic Test (AT) Interval
1 to 18 Months
12
BR1,TIN
Date For Next Automatic Test
yyyy-mm-dd
1/1/2099
BR1,ATD
Start Time For Automatic Test
0 to 23
0
BR1,ATH
Hours To Wait From Last BD Before
AT
0 to 240 hours
72
BR1,ATW
Manual Test Type
disabled, 20%, timed
"disabled"
BR1,MTT
Reserve Time Low (Full Capacity)
0.0 to 99.9 hours
0
RTL1,THR
Real-time Reserve Low (During BD)
0.0 to 99.9 hours
0
RRTL1,THR
Battery Sections
String 1 contactor
CN1 to CN4
"DCN01"
B01,CON
String 1 Number of strings
1 to 70
0
B01,NST
String 1 Battery type
"VALVE-REG"
B01,BTY
String 2 contactor
CN1 to CN4
"DCN01"
B02,CON
String 2 Number of strings
1 to 70
0
B02,NST
String 2 Battery type
"VALVE-REG"
B02,BTY
String 3 contactor
CN1 to CN4
"DCN01"
B03,CON
String 3 Number of strings
1 to 70
0
B03,NST
String 3 Battery type
"VALVE-REG"
B03,BTY
Battery Boost
Boost Maximum Duration
1 to 80 Hours
1
BS1,TMD
Automatic Boost Feature
disabled, timed, or
current
"disabled"
BS1,ATM
Auto Boost BD Multiplication Factor
0.1 to 9.0
0.5
BS1,AMF
Auto Boost Termination Current
Threshold
1 to 999A
5
BS1,CTA
Shunt Monitors
Plant Shunt Type
Battery/None /Load
"BATTERY"
DCMC1,TYP
Plant Shunt Current Rating
0 to 9999 Amps
600
DCMC1,SHA
ID1 Type
Battery/None /Load
"BATTERY"
DCM01,TYP
ID1 Shunt Current Rating
0 to 9999 Amps
300
DCM01,SHA
ID2 Type
Battery/None /Load
"NONE"
DCM02,TYP
ID2 Shunt Current Rating
0 to 9999 Amps
300
DCM02,SHA
ID3 Type
Battery/None /Load
"NONE"
DCM03,TYP
ID3 Shunt Current Rating
0 to 9999 Amps
600
DCM03,SHA
ID4 Type
Battery/None /Load
"NONE"
DCM04,TYP
ID4 Shunt Current Rating
0 to 9999 Amps
600
DCM04,SHA
ID5 Type
Battery/None /Load
"NONE"
DCM05,TYP
ID5 Shunt Current Rating
0 to 9999 Amps
600
DCM05,SHA
ID6 Type
Battery/None /Load
"NONE"
DCM06,TYP
ID6 Shunt Current Rating
0 to 9999 Amps
600
DCM06,SHA