Table d-2 24v battery related items defaults – GE Industrial Solutions Pulsar Plus Controller User Manual
Page 183

Pulsar Plus Controller Family
Issue 7 December 2011
183
Table D-2 24V Battery Related Items Defaults
Category
Description
Range
Valve-Reg
Flooded
Li_ELiTE
NiCd
Li-LMP
obj,attr
Voltage Settings
Float Rectifier High Voltage Shutdown
25 to 30V
29.25
29.25
29.25
29.25
29.25
GM1,FSD
Float High Voltage Major Alarm
25.74 to 31.75V
28.24
28.24
28.24
28.24
28.24
HVA1,FTH
Float High Voltage Minor Alarm
24.75 to 29.75V
27.74
27.74
27.74
27.74
27.74
HFV1,FTH
Float Voltage
21 to 28V
27.24
26.04
27.24
27.20
27.24
GM1,FSP
Float Battery on Discharge Alarm
23 to 28V
25.54
25.00
26.50
25.54
25.54
BDA1,FTH
Very Low Voltage Alarm
20 to 25.5V
23.00
23.00
23.00
23.00
23.00
VLA1,THR
Rectifier On Threshold
20 to 25V
22.00
22.00
22.00
22.00
22.00
DC1,ROT
Battery Disconnect
LV Battery Disconnect
1=Enabled
0=Disabled
1
1
0
1
0
CN1,ENA
LV Battery Disconnect Voltage
19.5 to 25V
21.00
21.00
21.00
21.00
21.00
CN1,DTH
LV Battery Reconnect Voltage
19.5 to 25V
22.20
22.20
22.20
22.20
22.20
CN1,RTH
Batteries
Cells Per String
0-75
12
12
12
12
12
DC1,CPS
String End Of Discharge Voltage
19.25 to 25.35
21.00
21.00
21.00
21.00
21.00
BR1,CEV
Recharge Current Limit Feature
1=Enabled
0=Disabled
0
0
0
0
0
BR1,CLE
Recharge Current Limit Value
5 to 1000A
50
50
25
25
25
BR1,CLT
Boost Maximum Duration
1 to 80 Hours
1
1
1
1
1
BS1,TMD
Voltage Imbalance Detect
1.5V to 3.0V
1.7
1.7
1.7
2.0
1.7
BR1,SCV
High Temperature Disconnect
30 to 90
o
C
75
75
75
75
75
BR1,TTH
High Battery Temperature
30 to 85
o
C
55
55
55
55
85
BTHA1,THR
Battery Slope
Compensation
Slope Thermal Compensation (STC)
1=Enabled
0=Disabled
1
0
0
0
0
SC1,STT
High Temperature Voltage Step Down
45 to 85
o
C
75
75
75
75
75
SC1,SPT
High Temperature Compensation Stop
30 to 55
o
C
55
55
55
55
55
SC1,UTT
High Temperature Decrease Rate
1-10mV/
o
C per
cell
3
3
3
3
3
SC1,USP
Nominal Temperature (No Temp
Comp)
15 to 30
o
C
25
25
25
25
25
SC1,NTT
Low Temperature Compensation
Feature
1=Enabled
0=Disabled
0
0
0
0
0
SC1,RVE
Low Temperature Compensation Stop
-5 to 20
o
C
0
0
0
0
0
SC1,LTT
Low Temperature Decrease Rate
1-10mV/
o
C per
cell
3
3
3
3
3
SC1,LSP
Battery Discharge Test
Timed Test Alarm Voltage Threshold
21 to 27V
22.00
22.00
23.00
22.00
22.00
BR1,TEV
Rectifier Voltage During Battery Test
21 to 26V
21.00
21.00
21.00
21.00
21.00
BR1,BTV
Battery Boost
Boost Rectifier High Voltage Shutdown
26 to 30V
29.25
29.25
29.25
29.25
29.25
GM1,BSD
Boost High Voltage Major Alarm
25.75 to 31.75V
28.24
29.00
28.24
28.24
28.24
HVA1,BTH
Boost High Voltage Minor Alarm
25.75 to 31.75V
27.74
28.00
27.74
27.74
27.74
HFV1,BTH
Boost Voltage
22 to 30V
27.24
26.04
27.24
27.20
27.24
GM1,BSP
Boost Battery on Discharge Alarm
23 to 28V
25.54
25.00
26.50
25.54
25.54
BDA1,BTH