Table d-1 standard configuration item defaults – GE Industrial Solutions Pulsar Plus Controller User Manual
Page 172

Pulsar Plus Controller Family
Issue 7 December 2011
172
Table D-1 Standard Configuration Item Defaults
Factory Default
Factory 24V
Rectifier
Default
Factory 48V
Rectifier
Default
Category
Description
Range
Factory
Factory 24V
Factory 48V
obj,attr
Controller
Site ID
≤ 20 characters
""
PS1,SID
Site Description
≤ 55 characters
""
PS1,SDE
Controller Description
Plant Description
"NE843A"
PS1,DES
System Description
≤ 55 characters
"Infinity NE"
PS1,SYS
Plant Description
Plant Description
"H569-2448"
DC1,DES
Plant Voltage Type
24V or 48V
"24V"
"48V"
DC1,TYP
Automatic Daylight Savings Feature
1=Enabled
0=Disabled
1
PS1,DLS
Display Contrast
0 to 100%
50
PS1,DCT
Temperature Display Units
C or F
"C"
PS1,TUN
Date Format
"MM/DD/YYYY"
PS1,DTF
Time Format
12 or 24
12
PS1,TMF
Front Panel Configuration
1=Enabled
0=Disabled
1
PS1,FPC
Remote rectifier Off
1=Enabled
0=Disabled
0
PS1,RRF
Emergency Power-off Enable
1=Enabled
0=Disabled
1
PS1,POE
User Name Login Enable
1=Enabled
0=Disabled
0
PS1,USR
Front Panel PIN enable
1=Enabled
0=Disabled
0
PS1,FPE
Front Panel Pin Default
Four digits 0-9
"0000"
PS1,FPP
Front Panel PIN timeout
1 to 120 minutes
30
PS1,FPT
Daylight Saving Start
mon:wk:dow:min
mon:-1:dom:min
"3:2:0:120"
PS1,DSS
Daylight Saving End
mon:wk:dow:min
mon:-1:dom:min
"11:1:0:120"
PS1,DSE
Uninstall Equipment Timeout
0 to 60s
15
PS1,UET
Controller Ambient Temperature
High
35 to 75
c
C
75
AMTH1,THR
Controller Ambient Temperature
Low
-40 to 10 C
-40
AMTL1,THR
Critical Equals Major
1=Enabled
0=Disabled
1
PS1,CEM
User Password
"lineage"
PAS U,
Super-user Password
"super-user"
PAS S,
Administrator Password
"administrator"
PAS A,
Low Voltage
Disconnects
Battery Disconnect Control Mode
0=none, 1=voltage
2=voltage/time
1
CN1,DAM
Battery Disconnect 1
Battery Disconnect Time Delay
0 to 300 minutes
0
CN1,DDY
Battery Reconnect Control Mode
0=none, 1=voltage
2=voltage/time
1
CN1,RAM
Battery Reconnect Time Delay
0 to 300 sec
0
CN1,RDY
Battery Disconnect Description
<=32 Chars
"LVBD1"
CN1,DES
Battery Disconnect Open
Description
<=32 Chars
"LVBD1 Open"
CNO1,DES
Battery Disconnect Open Front
Panel Description
<=32 Chars
"LVBD1 Open"
CNO1,FDS
Battery Disconnect Failed
Description
<=32 Chars
"LVBD1 Failed"
CNF1,DES
Battery Disconnect Failed Front
Panel Description
<=32 Chars
"LVBD1 Failed"
CNF1,FDS
Load Disconnect 1
Load 1 Disconnect
1=Enabled
0=Disabled
1
CN2,ENA