Table 46 T1.317 Power System Related Commands
obj,attr
description
sta
cha ope
type
Range of Values
ps1,sys
System Description
text
Up to 55 characters
ps1,swv
Software version
text
d.d
ps1,verw
Web pages version
text
d.d
ps1,verb
Boot block version
text
d.d
ps1,verd
Display version
text
d.d
ps1,dflt
Defaults version
text
d.d
ps1,brc
Board code
text
“”
ps1,sn
Serial number
text
YYLLdddddddd
ps1,dow
Day of week
Text
Sunday…Saturday
ps1,dat
Date
date
format matching ps1,dtf
ps1,dtf
Date format
text
mm-dd-yyyy, dd-mm-yyyy, yyyy-
mm-dd
ps1,tim
Time
time
hh:mm
ps1,tmf
Time format
number 12, 24
ps1,dls
Daylight savings enable
number 0=disabled 1=enabled
ps1,lng
Language
text
ENGLISH, OTHER
OPE changes the descriptions
ps1,tun
Temperature units
text
C, F
Ps1,cem
Critical equals major
number 0=disable, 1=enable
ps1,fpc
Front panel configuration
number 0=disable, 1=enable
ps1,rrf
Remote rectifier off
number 0=disable, 1=enable
ps1,poe
Power off enable
number 0=disable, 1=enable
ps1,usl
Uninstall missing equipment
number 1
ps1,usr
Username enable
number 0=disable, 1=enable
ps1,dct
Display contrast
number 0 – 100 %
ps1,ptt
Communication port type
text
“LOCAL”,”MODEM”
ps1,amt
System ambient temperature
number dd °C
ps1,fst
Factory defaults
text
See ps1,fstl
ps1,fstl
Factory defaults list
text
Comma deliminated list of
defaults
ps1,rap
Reset Passwords
number 1 = reset passwords (OPE only
valid from local display) will
restore passwords.gal
ps1,fpe *
Front Panel Pin enable
number 0=disable, 1=enable
ps1,fpt *
Front Panel Pin Time-out
Number 1-120 minutes
Ps1,fpp *
Front Panel Pin
Number 4 digit Pin (only viewable as
admin)
ps1,rss
Restart all
number 1=restart rectifiers and ringers
ps1,ltt
Lamp test
number 1 = do lamptest
ps1,ast
System alarm state
Text
“NORM, "RO", "WRN", "MIN",
"MAJ", "CRIT"
ps1,slv
Port security level
text
ps1,dss
Daylight saving start
d:d:d:d
mon:wk:dow:min
mon:-1:dom:min
ps1,dse
Daylight saving end
d:d:d:d
mon:wk:dow:min
mon:-1:dom:min
Ps1,uet
Uninstall Timeout
Number 0-60
* Must have administrator privileges to change.