Table 54 t1.317 converter plant related commands – GE Industrial Solutions Pulsar Plus Controller User Manual
Page 146
Pulsar Plus Controller Family
Issue 7 December 2011
146
Table 53 T1.317 Rectifiers Related Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
gsr,adc
DC Current (VI, VIR)
number number A
gsr,vdc
DC Voltage
number number V
gsr,stt
Individual rectifier state
text
ON*, OFF, STANDBY*,
VACANT*, MISSING
gsr,cap
Capacity
number number A
gsr,tmp
Temperature
number number F or C
gsr,seq
Use In Sequence Enable
number 0=no 1=yes
gsr,rfa
Rectifier Fail
number 0=inactive 1=active
gsr,acf
AC Fail
number 0=inactive 1=active
gsr,man
Standby or Manual Off
number 0=inactive 1=active
gsr,did
ID Conflict
number 0=inactive 1=active
gsr,clm
Current Limit
number 0=inactive 1=active
gsr,rcf
Communication Fail
number 0=inactive 1=active
gsr,rfn
Fan fail
number 0=inactive 1=active
s stands for shelf number (1 to 6)
r stands for rectifier number (1 to 7)
* The user may only set the state to ON, STANDBY, or VACANT
Table 54 T1.317 Converter Plant Related Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
cp1,des
Description
Text
Converter Plant 1
cp1,typ
Converter output type
Text
24V or 48V
cp1,vdc
DC Voltage
Number Number in volts
cp1,adc
DC Current
Number Number in amps
cp1,cap
Installed capacity
Number Number in amps
cp1,olcap
Online capacity
Number Number in amps
cp1,vsp
Voltage Set-Point
Number 23-28V or 46-57V
cp1,vsd
Internal high voltage shutdown
Number 25-30V or 50-60V
cp1,dth
Low Voltage Discon Threshold
Number 20-25V or 40-50V
cp1,rth
Low Voltage Recon Threshold
Number 22-27V or 44-54V
cp1,lvd
Low Voltage Disconnect Enable
Number 0=disabled 1=enabled
cp1,rss
Converter restart
number 1=restart
cp1,rme
Redundancy monitor enable
number 0=disable,1=enable
Cp1,rof
Remote standby enable
number 0=disable,1=enable