Table D-1 Standard Configuration Item Defaults
Factory Default
Factory 24V
Rectifier
Default
Factory 48V
Rectifier
Default
Category
Description
Range
Factory
Factory 24V
Factory 48V
obj,attr
Local RS-232 handshaking (Flow
Control)
No/SW/HW
"NO"
LP1,HSH
Number of Local RS-232 data bits
7,8
8
LP1,DBT
Local RS-232 parity
n,e,o
N
LP1,PRY
Number of Local RS-232 stop bits
1,2
1
LP1,SBT
Local RS-232 Time-out
0-45 minutes
5
LP1,TMO
Local RS-232 Application
TERMINAL,
EVENT LOG
"TERMINAL"
LP1,APP
Modem Port Write Access
1=Enabled
0=Disabled
1
MP1,WRE
Modem baud rate
2400/4800/ 9600
"2400"
MP1,BDR
Number Of Modem data bits
7,8
8
MP1,DBT
Modem parity
n,e,o
N
MP1,PRY
Number Of Modem stop bits
1,2
1
MP1,SBT
Modem Time-out
0-45 minutes
5
MP1,TMO
Modem initialization string
≤ 20 Characters
"AT&FEV&C1S0=0H"
MP1,INS
Modem number of rings before
answering
1 to 9
1
MP1,NRG
Modem handshaking (Flow Control)
No/SW/HW
"NO"
MP1,HSH
Network Port
DHCP
0=static
1=client
2=server
1
NET1,DHCP
Timeout
0 to 45 minutes
10
NET1,TMO
Network Port Write Access
1=Enabled
0=Disabled
1
NET1,WRE
Standard Alarms
Alarm Delay
0 to 9 minutes
0
SDA,DLY
Notify On Occur
1=Enabled
0=Disabled
0
SDA,NOO
Notify On Retire
1=Enabled
0=Disabled
0
SDA,NOR
Nag On Occur
1=Enabled
0=Disabled
0
SDA,NAG
Notify Destination
""
SDA,DST
Single Threshold
Alarms
Alarm Delay
0 to 9 minutes
0
THA,DLY
Notify On Occur
1=Enabled
0=Disabled
0
THA,NOO
Notify On Retire
1=Enabled
0=Disabled
0
THA,NOR
Nag On Occur
1=Enabled
0=Disabled
0
THA,NAG
Notify Destination
""
THA,DST
Dual Threshold
Alarms
Alarm Delay
0 to 9 minutes
0
DTA,DLY
Notify On Occur
1=Enabled
0=Disabled
0
DTA,NOO
Notify On Retire
1=Enabled
0=Disabled
0
DTA,NOR
Nag On Occur
1=Enabled
0=Disabled
0
DTA,NAG
Notify Destination
""
DTA,DST
Alarm Call-Out
Nag Interval
15 to 60 minutes
15
CM1,NGI
Call-Out Destination Type
data or pager
"DATA"
COP,TYP
Call-Out Phone Number
up to 25 Characters
""
COP,PHN
Call-Out Baudrate
300, 1200, 2400,
4800, 9600, 19200
2400
COP,BDR
Call-out Data Bits
7 or 8
8
COP,DBT