Figure 22: typical alarm connections, Table 41 es772 connector j1 pinout definitions, Table 42 es772 connector j3 pin definitions – GE Industrial Solutions Pulsar Plus Controller User Manual
Page 112

Pulsar Plus Controller Family
Issue 7 December 2011
112
Table 41 ES772 Connector J1 Pinout Definitions
Pin
Name
Definition
Comments/Connections
1
VPWR +
V(+) Power
Power for ES772A, connect to VBus(+)
2
N/A
Reserved
3
N/A
Reserved
4
SHUNT-
Neg Batt Shunt Input
Polarity is during battery discharge
5
BATT1_SENSE
Polarity Sense for String 1
Connect to battery negative, V(-) of String 1
6
DIST_ALM_1
Trip-Indicator Input-1 for US
Style CB or GMT Fuse. Alarm
on closure to VBus(-).
Connect to NC terminal of breaker micro switch or to
indicator lead of GMT fuse, other end (C) referenced to
VBus(-).
7
EXT BAT SW1
Alarm input for external
battery disconnect switch;
alarm on closure to VBus(-).
Connect to NC micro switch of US Style CB, other end
(C) referenced to VBus(-), micro switch must close upon
manual opening of CB.
8
VPWR -
V(-) Power
Power for ES772A, connect to VBus(-)
9
STATUS1_RTN
Reference for STATUS1
Connect to C pin of micro switch of Contactor 1.
10 STATUS1
Contactor 1 Status Monitor
Connect to NO pin of micro switch of Contactor 1.
11 SHUNT+
Positive Battery Shunt Input
Polarity is during battery discharge
12 LVD1_COIL
Contactor 1 coil input
Connect to one side of Contactor 1 coil, other side of
coil connected to VBus(+).
13 DIST_ALM_2
Trip-Indicator Input-2 for US
Style CB or GMT Fuse. Alarm
on closure to VBus(-).
Connect to NC terminal of breaker micro switch or to
indicator lead of GMT fuse, other end (C) referenced to
VBus(-).
14 EXT BAT SW2
Alarm input for external
battery disconnect switch;
alarms on closure to VBus(-).
Connect to NC micro switch of US Style CB, other end
(C) referenced to VBus(-), micro switch must close upon
manual opening of CB.
Table 42 ES772 Connector J3 Pin Definitions
Pin
Name
Definition
Comments
1
BATT2_SENSE
Polarity Sense for String 2.
Connect to battery negative VBus(-) of string 2.
2
STATUS2_RTN
Reference for STATUS2.
Connect to C pin of micro switch of Contactor 2.
3
STATUS2
Contactor 2 Status Monitor.
Connect to NO pin of micro switch of Contactor 2.
4
LVD2_COIL
Contactor 2 coil input.
Connect to one side of Contactor 2 coil, other side of
coil connected to VBus(+).
Figure 22: Typical Alarm Connections