GE Industrial Solutions Pulsar Plus Controller User Manual
Page 143
Pulsar Plus Controller Family
Issue 7 December 2011
143
objid,acc
Contact Closure
text
R1,R2,R3,R4,R5,R6,R7,””
objid,dly
Notify Delay
number 0-540 seconds
objid,noo
Notify On Occur
number 0=no 1=yes
objid,nor
Notify On Retire
number 0=no 1=yes
objid,nag
NAG On Occur
number 0=no 1=yes
objid,dst
Notify Destination
text
“”, P1, P2, P3, P4, E1, E2, E3, E4,
S1, S2, S3, S4
objid
Description
Float Threshold
Boost Threshold
bda1
Battery On Discharge
23-28 V
or 46-55 V
23-28 V
or 46-55 V
hfv1
High voltage
24.75-29.75 V
or 50-60 V
25.75-31.75 V
or 52-60 V
hva1
Very high voltage
24.75-29.75 V
or 50-60 V
25.75-31.75 V
or 52-60 V
Table 50 T1.317 Alarms With One Threshold Related Command
obj,attr
Description
sta
cha
ope
type
Range of Values
objid,ide
Identifier
text
see below
objid,des
Description
text
see below
objid,fds
Front Panel Description
text
see below
objid,ast
Alarm state
number 0=not active 1=active
objid,sev
Alarm severity
text
CRIT, MAJ, MIN, WRN, RO
objid,thr
Alarm threshold
number number
objid,led
LED
text
BD,AC,DC,””
objid,acc
Contact Closure
text
R1,R2,R3,R4,R5,R6,R7,””
objid,dly
Notify Delay
number 0-540 seconds
objid,noo
Notify On Occur
number 0=no 1=yes
objid,nor
Notify On Retire
number 0=no 1=yes
objid,nag
NAG On Occur
number 0=no 1=yes
objid,dst
Notify Destination
text
“”, P1, P2, P3, P4, E1, E2, E3, E4,
S1, S2, S3, S4
objid
Description
Threshold
amth1
High ambient temp
30-75C
amtl1
Low ambient temp
-40-10C
btha1
High battery temperature
30-85C
mrfa1
Multiple Rectifier Fail
2-88
mman1
Multiple Manual Off
2-88
rrtl1
Real-time reserve low
0-100hrs
rtl1
Reserve time low
0-100hrs
macf1
Multiple AC Fail
2-88
rls1
Redundancy Loss
1-87
cmfa1
Multiple Converter Fail
2-16
chva1
Converter Very High Output Voltage
25-30V
50-60V
chfv1
Converter High Output Voltage
24-30V
48-60V
cvla1
Converter Very Low Output Voltage
20 - 27V
40 - 54V
crl1
Converter redundancy loss
1-16
vla1
Very low voltage
20-25.5 V
or 40-51 V