Table d-1 standard configuration item defaults – GE Industrial Solutions Pulsar Plus Controller User Manual
Page 173

Pulsar Plus Controller Family
Issue 7 December 2011
173
Table D-1 Standard Configuration Item Defaults
Factory Default
Factory 24V
Rectifier
Default
Factory 48V
Rectifier
Default
Category
Description
Range
Factory
Factory 24V
Factory 48V
obj,attr
Load 1 Disconnect Control Mode
0=none, 1=voltage
2=voltage/time
1
CN2,DAM
Load 1 Disconnect Voltage
19.5 to 25V
-39.0 to -50V
21.00
42.00
CN2,DTH
Load 1 Disconnect Time Delay
0 to 300 minutes
0
CN2,DDY
Load 1 Reconnect Control Mode
0=none, 1=voltage
2=voltage/time
1
CN2,RAM
Load 1 Reconnect Voltage
19.5 to 27
-39.0 to -55.0V
22.00
44.00
CN2,RTH
Load 1 Reconnect Time Delay
0 to 300 sec
0
CN2,RDY
Load 1 Disconnect Description
<=32 Chars
"LVLD1"
CN2,DES
Load 1 Disconnect Open Description
<=32 Chars
"LVLD1 Open"
CNO2,DES
Load 1 Disconnect Open Front Panel
Description
<=32 Chars
"LVLD1 Open"
CNO2,FDS
Load 1 Disconnect Failed
Description
<=32 Chars
"LVLD1 Failed"
CNF2,DES
Load 1 Disconnect Failed Front
Panel Description
<=32 Chars
"LVLD1 Failed"
CNF2,FDS
Load Disconnect 2
LV Load 2 Disconnect
1=Enabled
0=Disabled
0
CN3,ENA
LV Load 2 Disconnect Control Mode
0=none, 1=voltage
2=voltage/time
1
CN3,DAM
LV Load 2 Disconnect Voltage
19.5 to 25V
-39.0 to -50V
21.00
42.00
CN3,DTH
LV Load 2 Disconnect Time Delay
0 to 300 minutes
0
CN3,DDY
LV Load 2 Reconnect Control Mode
0=none, 1=voltage
2=voltage/time
1
CN3,RAM
LV Load 2 Reconnect Voltage
19.5 to 27
-39.0 to -55.0V
22.00
44.00
CN3,RTH
LV Load 2 Reconnect Time Delay
0 to 300 sec
0
CN3,RDY
Load 2 Disconnect Description
<=32 Chars
"LVLD2"
CN3,DES
Load 2 Disconnect Open Description
<=32 Chars
"LVLD2 Open"
CNO3,DES
Load 2 Disconnect Open Front Panel
Description
<=32 Chars
"LVLD2 Open"
CNO3,FDS
Load 2 Disconnect Failed
Description
<=32 Chars
"LVLD2 Failed"
CNF3,DES
Load 2 Disconnect Failed Front
Panel Description
<=32 Chars
"LVLD2 Failed"
CNF3,FDS
Load Disconnect 3
Load 3 Disconnect
1=Enabled
0=Disabled
0
CN4,ENA
Load 3 Disconnect Control Mode
0=none, 1=voltage
2=voltage/time
1
CN4,DAM
Load 3 Disconnect Voltage
19.5 to 25V
-39.0 to -50V
21.00
42.00
CN4,DTH
Load 3 Disconnect Time Delay
0 to 300 minutes
0
CN4,DDY
Load 3 Reconnect Control Mode
0=none, 1=voltage
2=voltage/time
1
CN4,RAM
Load 3 Reconnect Voltage
19.5 to 27
-39.0 to -55.0V
22.00
44.00
CN4,RTH
Load 3 Reconnect Time Delay
0 to 300 sec
0
CN4,RDY
Load 3 Disconnect Description
<=32 Chars
"LVLD3"
CN4,DES
Load 3 Disconnect Open Description
<=32 Chars
"LVLD3 Open"
CNO4,DES
Load 3 Disconnect Open Front Panel
Description
<=32 Chars
"LVLD3 Open"
CNO4,FDS
Load 3 Disconnect Failed
Description
<=32 Chars
"LVLD3 Failed"
CNF4,DES
Load 3 Disconnect Failed Front
Panel Description
<=32 Chars
"LVLD3 Failed"
CNF4,FDS