Table E-1 Alarms, Alarm Relays and LEDs Assignments – Pulsar Display
Severity - Relay and Display
Additional Relay
LED
Description
CRIT
PMJ
PMN
WRN
RO
R1
R2
R3
R4
R5
R6
R7
AC
DC
BD
Object
ID
No Dial-Out Response
WRN
POR1
Open String
MAJ
DC
OSA1
Password At Default
RO
PFD1
Processor Halt
RO
PHT1
Program Line Invalid
MAJ
PGI1
Queue Overflow
WRN
COF1
Real-Time Reserve Time Low
RO
RRTL1
Rectifier Current Limit
RO
CLM1
Rectifier Fail
MIN
R5
RFA1
Rectifier Fan Fail
MIN
R5
RFN1
Rectifier Redundancy Loss
MIN
R5
RLS1
Reserve Time Low
RO
RTL1
Ringer External Failure Major
MAJ
RPXJ1
Ringer External Failure Minor
MIN
RPXN1
Ringer Fail Major
MAJ
RPFJ1
Ringer Fail Minor
MIN
RF1
Ringer Fan Fail
MIN
RPFF1
Ringer ID Conflict
MAJ
RCDP1
Ringer Redundancy Loss
MIN
RPRL1
Self Test Failed
MIN
STF1
Sense Fuse
MIN
VSF1
Thermal Probe Failure
MIN
TPA1
Unconfigured Alarm Destination
WRN
NNC1
Un-powered Controller (Not
configurable)
x
x
x
x
x
x
x
Very High Battery Temperature
RO
BTVH1
Very Low Battery Temperature
RO
BTVL1
Very Low Voltage
CRIT
R2
VLA1
Voltage Duplicate ID
MAJ
MDP1
Voltage ID Not Configured
MAJ
MZD1
Voltage Imbalance Detect
MIN
SCD1
Voltage Monitoring Module Failure
MIN
VMF1
Table E-2 Alarms, Alarm Relays and LEDs Assignments – Phoenix Display
Severity - Relay and Display
Additional Relay
LED
Description
CRIT
PMJ
PMN
WRN
RO
R1
R2
R3
R4
R5
R6
R7
Object
ID
AC Fail
PMN
R1
ACF
ACF1
Alarm Cut-off Active
RO
ACO
AAC1
Alarm Test Aborted
RO
ATB1
Alarm Test Active
RO
ATA1
Auxiliary 1
MAJ
AUX1
Auxiliary 2
MAJ
AUX2
Auxiliary 3
MAJ
AUX3
Auxiliary 4
MAJ
AUX4
Auxiliary 5
MAJ
AUX5