Chapter 4 Operation of the Server
4-19
4.4.10
Shutdown Wait Time Administration
The shutdown wait time administration is a setting to delay the shutdown start by
specifying the shutdown start time when a power failure has occurred in the system
with the UPS.
■
Command operation
1. Use the showshutdowndelay (8) command to display the shutdown wait time.
XSCF> showshutdowndelay
UPS shutdown wait time : 500 second(s)
2. Use the setshutdowndelay (8) command to set the shutdown wait time. Set
the shutdown wait time from 0 to 9999 (sec). The default is "10 sec."
XSCF> setshutdowndelay -s 600
4.4.11
Dual Power Feed Administration
The dual power feed is a type of power feed for high-reliability systems that contain
dual lines to the power supply. If one line has stopped, the other line does not stop
and enables the system to continue operation. The dual power feed is enabled and
disabled by an XSCF Shell command. This setting is done by FEs.
Note –
Enabling and disabling the dual power feed is the setting for only midrange
systems. In high-end systems, the dual power feed is optional. If you use the option,
the dual power feed is enabled.
■
Command operation
1. Use the showdualpowerfeed (8) command to display the current setting
status of the dual power feed.
XSCF> showdualpowerfeed
Dual power feed is disabled.