This topic lists the physical specifications for your server.
Dimensions
Width without rack handles: 447 mm (17.6 inches)
Width with rack handles: 482 mm (18.98 inches)
Depth without rack handles and power supply handles: 764 mm (29.37 inches)
Depth with rack handles and power supply handles: 782.9 mm (30.82 inches)
Height: 87 mm (3.43 inches)
Weight
The product weight varies depending on different system configurations.
Range of product weight without package: 16 kg (35.27 lb) to 32 kg (70.55 lb)
Range of product weight with package: 24.7 kg (54.45 lb) to 40.7 kg (89.73 lb)
Environment
The following table provides information about the ASHRAE class A2, class A3, and class A4 specifications.
Table 1. ASHRAE class A2, class A3, and class A4 specifications
ASHRAE class A2
ASHRAE class A3
ASHRAE class A4
Air temperature
(operating)
10°C to 35°C (50°F to 95°F)
5°C to 40°C (41°F to 104°F)
5°C to 45°C (41°F to 113°F)
Air temperature
(storage)
40°C to 60°C (-40°F to
140°F) in original shipping
package
40°C to 60°C (-40°F to
140°F) in original shipping
package
40°C to 60°C (-40°F to
140°F) in original shipping
package
Humidity (operating)
8% to 80%
(non-condensing)
8% to 85%
(non-condensing)
8% to 90%
(non-condensing)
Humidity (storage)
8% to 90%
(non-condensing)
8% to 90%
(non-condensing)
8% to 90%
(non-condensing)
Altitude
0 to 3048 m (0 to 10 000 ft) in an unpressurized environment
Note: When the altitude exceeds 900 m (2953 ft), the defined maximum dry-bulb
temperature for operation becomes a dependent variable.
A2: The temperature value decreases by 1°C (33.8°F) with every 300 m (984 ft) of
altitude increase.
A3: The temperature value decreases by 1°C (33.8°F) with every 175 m (574 ft) of
altitude increase.
A4: The temperature value decreases by 1°C (33.8°F) with every 125 m (410 ft) of
altitude increase.
12