2.2 Basic Module
2.2.4 218IFA Module (Ethernet)
2-20
Message Communication Item of Connection Parameter Setting
Sets the connection parameters for the message communication using MSG-SND/MSG-RCV function and the
message communication using automatic receive function.
The following table shows each setting item.
Item
Setting Range
Details
Default
Easy Setting
–
Opens the easy setting screen for the connection parameters. The
content of the selected connection is shown.
–
Connection Number
(CNO)
1 to 4
In 218IFA Ethernet communication, remote stations are distin-
guished by their connection numbers.
This connection number is used in remote connection number
(PARAM02) of the parameter list (PARAM) of the MSG-SND/
MSG-RCV function.
–
Local Port
256 to 65535
Specify the 218IFA port number for each connection. The 218IFA
module establishes a message communication with the connection
with this port number only. Set an unique channel number for the
port number of this connections.
Also, to delete the port number, enter zero.
Note: When the connection type = UDP, the port number cannot be
9998 or 10000.
0
Node IP Address
0.0.0.0 to
255.255.255.254
Set the remote IP address for each connection. However, the fol-
lowing addresses are excluded:
127.xxx.xxx.xxx
xxx.xxx.xxx.000 (except 000.000.000.000)
xxx.xxx.xxx.255
Note: When 0.0.0.0 is set, it will enter into “Unpassive open
mode.” When the 218IFA module is within the network
specified by the subnet mask, it responds to the connection
request from the remote station regardless of the remote IP
address setting.
000.000.000.0
00
Node Port
0 and
256 to 65535
Specify the remote port number for each connection. A pair of
remote IP address and remote port number must not be duplicated.
Note: In case of “Unpassive open mode,” set it to zero.
0
Connect Type
TCP,
UDP
Select a transport layer protocol.
TCP: Transmission control protocol
UDP: User datagram protocol
TCP
Protocol Type
Extended
MEMOBUS,
MEMOBUS,
MELSEC,
None,
MODBUS/TCP
Select an application layer protocol.
Extended
MEMOBUS
Protocol Type
Overview
Extended
MEMOBUS
Yaskawa’s Extended MEMOBUS protocol.
MEMOBUS
Yaskawa’s MEMOBUS protocol.
MELSEC
Ethernet I/F protocol for the sequencer (A
series) manufactured by Mitsubishi Elec-
tric Corporation.
Non-procedure
General-purpose message communication.
Transmits and receives continuous data
intact in the specified register.
MODBUS/TCP
Industrial Ethernet protocol proposed by
Modicon, Inc.