A-58, 2 ) process result (param00) – Yaskawa MP2300S Basic Module User Manual
Page 380

Appendix G MSG-SND/MSG-RCV Functions (Ethernet)
G.1 Message Transmit Function (MSG-SND)
A-58
( 2 ) Process Result (PARAM00)
Process result is output to the upper byte. Lower byte is used for system analysis.
When an error occurs, take corrective action by referring to the following error contents:
Value of Process
Result
Meaning
00H
In process (Busy)
10H
Process completed (Complete)
8yH
Error occurred (Error)
Value of
Process Result
Error Contents
Description
80H
–
Reserved
81H
Function code error
Unused function code was transmitted or received.
Check PARAM04 (function code).
82H
Error in setting address
The following setting is out of the setting range. Check the setting.
PARAM05 (data address)
PARAM08 (coil offset)
PARAM09 (input relay offset)
PARAM10 (input register offset)
PARAM11 (holding register offset)
83H
Data size error
The transmit or receive data size is out of the setting range.
Check PARAM04 (data size).
84H
Error in setting circuit number
The circuit number is out of the setting range.
Check Cir-No (circuit number) of the MSG-SND function.
85H
Error in setting channel number
The communication buffer channel number is out of the setting range.
Check Ch-No (communication buffer channel number) of the MSG-SND
function.
86H
Connection number error
The connection number is out of the setting range.
Check PARAM02 (connection number).
87H
–
Reserved
88H
Communication section error
An error response was returned from the communication section (commu-
nication device). Check the equipment connection.
In addition, confirm communication with the remote device.
89H
Device select error
Unavailable device is set.
Check Dev-Typ (communication device type) of the MSG-SND function.