Yaskawa MP2300S Basic Module User Manual
Page 202

6.2 Communication with Other MP Series
6.2.1 When the MP2300S Acts as Slave (automatic receive function is used)
6-13
Built-in Ethernet Communications
Parameter list setting example for the message transmit function
An example of a parameter list setting when writing 100 words of data from MW00000 to the destination using
the connection with a connection number = 1 follows:
Note: IN: Input, OUT: Output, SYS: For system use
Table 6.2 Sample Parameter List Setting (parameter list start address Param=DA00000)
Register
Number
Setting
Value
Parameter
Number
IN/OUT
Remarks
DW00000
–
PARAM00
OUT
Process result
DW00001
–
PARAM01
OUT
Status
DW00002
00001
PARAM02
IN
Connection number = 1
DW00003
–
PARAM03
IN
Option (Setting unnecessary)
DW00004
000BH
PARAM04
IN
Function code = 0BH (Writes to holding register)
DW00005
00000
PARAM05
IN
Data address = 0 (Starting from MW00000)
DW00006
00100
PARAM06
IN
Data size = 100 (100 words)
DW00007
00001
PARAM07
IN
Remote CPU number = 1
DW00008
00000
PARAM08
IN
Coil offset = 0 word
DW00009
00000
PARAM09
IN
Input relay offset = 0 word
DW00010
00000
PARAM10
IN
Input register offset = 0 word
DW00011
00000
PARAM11
IN
Holding register offset = 0 word
DW00012
–
PARAM12
SYS
Reserved by the system. (Zero clear at startup)
DW00013
–
PARAM13
SYS
Reserved by the system.
DW00014
–
PARAM14
SYS
Reserved by the system.
DW00015
–
PARAM15
SYS
Reserved by the system.
DW00016
–
PARAM16
SYS
Reserved by the system.