6.4 Communication with PLC Manufactured by Mitsubishi Electric Corporation (MELSEC protocol)
6.4.2 When the MP2300S Acts as Master (I/O message communication function is used)
6-88
( 2 ) How to Set up the Remote Equipment (MELSEC Q series) to Be Connected
This section explains the MELSEC Q series side procedure to set up for connecting the MP2300S with the MELSEC Q
series.
Note: MELSEC Q series are products manufactured by Mitsubishi Electric Corporation.
Contact Mitsubishi Electric Corporation for more information.
1.
Start up GX Developer.
2.
Create a new project.
3.
Set up network parameters (MELSECNET/Ethernet).
4.
Set up Ethernet operation.
5.
Set the open setting.
Caution
Set up a unique IP address in the network.
For the IP address, check with your network administrator.
Table 6.25 Network Parameter Setting (example)
Setting Item
Setting Details
Network Type
Ethernet
Start I/O No.
Any
Network No.
Any
Group No.
Any
Exchange Number
Any
Mode
Online
Table 6.26 Ethernet Operation Setting (example)
Setting Item
Setting Details
Communication Data Code Setting
Binary mode communication
Initial Timing Setting
Always waiting OPEN
IP Address
192.168.1.2
Transmit Frame Setting
Ethernet (V2.0)
TCP Alive Check Setting
Any
Permit Writing during RUN
Permitted
Table 6.27 Open Setting (example)
Setting Item
Setting Details
(connection number=1)
Setting Details
(connection number=2)
Protocol
TCP
TCP
Open System
Fullpassive
Fullpassive
Fixed Buffer
Any
Any
Procedure to Communicate with Fixed Buffer
Any
Any
Pairing Open
Any
Any
Check Alive
Any
Any
Local Port Number
2715H (10005)
2716H (10006)
Remote IP Address for Communications
192.168.1.1
192.168.1.1
Remote Port Number for Communications
2715H (10005)
2716H (10006)