3.2.2 Start Sequence
The MP930 makes a number of determinations at startup. If an error is detected, the ERR indi-
cator will flash and the error content will be indicated by the number of times the indicator
flashes. When the indicator is flashing, the CP-717 cannot be operated. For details on the error
content and the action to be taken, see Chapter 9 Troubleshooting. Table 3.2 shows the MP930
indicators.
Table 3.2 Indicators and Indicator Patterns
Type
Indicator
Meaning
RDY
RUN
ALM
ERR
BAT
ALM
Normal
Lit
Unlit
Unlit
Unlit
Unlit
The user program is stopped.
Lit
Lit
Unlit
Unlit
Unlit
The user program is executing normally.
Error
Lit
Lit
Lit
Lit
Unlit
Hardware reset status (while display is contin-
uing)
Unlit
Unlit
Unlit
Unlit
Unlit
During initial execution (while display is con-
tinuing)
Unlit
−
Unlit
Lit
Unlit
A serious error has occurred.
Unlit
Unlit
Unlit
Flash-
ing
Unlit
1.
Flashing once or twice: RAM error
2.
Flashing two or three times: ROM error
3.
Flashing three or four times: Peripheral
LSI error
Alarm
−
−
−
−
Lit
Battery alarm
Lit
Lit
Lit
Unlit
Unlit
1.
Calculation error
2.
I/O error
Reported to the system (S) register (no in-
dicator display)
Hardware status (power loss, RUN/STOP, test
mode, etc.)
Other
Flash-
ing
Flash-
ing
Unlit
Unlit
Unlit
Memory initialization has been completed for
the DIP switch settings.
RDY and RUN flash repeatedly at the
same time.
Unlit
Unlit
Lit
Unlit
Unlit
Offline test mode