9.1 Overview of Troubleshooting

9 -5

J

Indicator Details

The following describes details and remedies for indicators showing operating status and er-
rors in the MP930.

Classifi-

cation

Indicator

Indicator Details

Remedy

cation

RDY RUN ALM ERR

BAT

ALM

Normal

Unlit

Unlit

Unlit

Lit

Unlit

Hardware reset status

If this status continues for more than
a second the problem is a user pro

Unlit

Unlit

Unlit

Unlit

Unlit

Initializing/busy

a second, the problem is a user pro-
gram error or hardware failure.

Unlit

Lit

Unlit

Unlit

Unlit

Drawing A executing

Troubleshoot system errors.

Lit

Unlit

Unlit

Unlit

Unlit

User program stopped (Offline Stop
Mode)

This status will occur if a program is
stopped from the CP-717 or by turn-
ing OFF the RUN switch.

Lit

Lit

Unlit

Unlit

Unlit

User program executing normally

This status will occur during normal
operation.

Error

Unlit

Lit

Unlit

Lit

Unlit

Serious failure has occurred.

See Processing Flow When a User
Program Error Occurs
.

Lit

Unlit

Unlit

Lit

Unlit

1.

Program memory initialization in-
complete

2.

Improper scan time setting

S

Clear program memory from the
System Definition Screen on the
CP717.

S

If this does not restore the system,
then hardware has probably failed.

Unlit

Unlit

Unlit

Flash-
ing

Unlit

Hardware errors

No. of flashes

2: RAM diagnosis error
3: ROM diagnosis error
4: CPU function diagnosis error
5: FPU function diagnosis error

Troubleshoot system errors.