Troubleshooting

9.1.2 Indicator Errors

9 -6

Classifi-

cation

Remedy

Indicator Details

Indicator

Classifi-

cation

Remedy

Indicator Details

BAT

ALM

ERR

ALM

RUN

RDY

Warning

Lit

Battery alarm

Replace the battery.

Lit

Lit

Lit

Unlit

Unlit

1.

Operation error

See Operation Error Remedies.

2.

I/O error

See I/O Error Remedies.

3.

Wrong interrupt occurs

System register warning (no indicator
display)

1.

CP-717 connection data

See System Status.

display)

2.

Hardware status (power interrup-
tion, RUN/STOP, Test Mode, etc.)

See System Status.

Test
Mode

Unlit

Unlit

Unlit

Lit

Unlit

Hardware errors

No. of flashes

2: RAM diagnosis error
3: ROM diagnosis error
4: CPU function diagnosis error
5: FPU function diagnosis error
6: RTC interrupt time diagnosis error
7: WDT over time diagnosis error

Troubleshoot system errors.