9.2 System Errors

9 -17

Table 9.5 User Operation Error Status - 3

Name

Error
Code

Error Contents

User

System Default

Integer
Operation

0001H

Integer operation - underflow

Yes

−32768 [−32768]

Operation

0002H

Integer operation - overflow

Yes

32768 [32768]

0003H

Integer operation - division error

Yes

The A register remains
the same.

0009H

Double integer operation - underflow

Yes

−2147483648
[−2147483648]

000AH

Double integer operation - overflow

Yes

2147483648
[2147483648]

000BH

Double integer operation - division Error

Yes

The A register remains
the same.

000xH

Integer operation error within operation error pro-
cessing drawing (x = 1 to B)

No

Default indicated above.

Real
Number
Operation

0010H

Integer storage - non-numeric error

Yes

Store not executed.
[00000]

Operation

0011H

Integer storage - underflow

Yes

Store not executed.
[−32768]

0012H

Integer storage - overflow

Yes

Store not executed.
[+32768]

0021H

Integer storage - underflow

Yes

Store not executed.
[−1.0E+38]

0022H

Integer storage - overflow

Yes

Store not executed.
[1.0E+38]

0023H

Real number operation - division-by-zero error

Yes

Operation not executed.
The F register remains
the same.

0030H

Real number operation - invalid operation (non-nu-
meric)

No

Operation not executed.

0031H

Real number operation - exponent underflow

No

0.0

0032H

Real number operation - exponent overflow

No

Maximum value

0033H

Real number operation - division error (non-numer-
ic 0/0)

No

Operation not executed.

0034H

Real number storage - exponent underflow

No

Stores 0.0.

9