Yaskawa MP930 User Manual
Page 276

9.2 System Errors
9 -17
Table 9.5 User Operation Error Status - 3
Name
Error
Code
Error Contents
User
System Default
Integer
Operation
0001H
Integer operation - underflow
Yes
−32768 [−32768]
Operation
0002H
Integer operation - overflow
Yes
32768 [32768]
0003H
Integer operation - division error
Yes
The A register remains
the same.
0009H
Double integer operation - underflow
Yes
−2147483648
[−2147483648]
000AH
Double integer operation - overflow
Yes
2147483648
[2147483648]
000BH
Double integer operation - division Error
Yes
The A register remains
the same.
000xH
Integer operation error within operation error pro-
cessing drawing (x = 1 to B)
No
Default indicated above.
Real
Number
Operation
0010H
Integer storage - non-numeric error
Yes
Store not executed.
[00000]
Operation
0011H
Integer storage - underflow
Yes
Store not executed.
[−32768]
0012H
Integer storage - overflow
Yes
Store not executed.
[+32768]
0021H
Integer storage - underflow
Yes
Store not executed.
[−1.0E+38]
0022H
Integer storage - overflow
Yes
Store not executed.
[1.0E+38]
0023H
Real number operation - division-by-zero error
Yes
Operation not executed.
The F register remains
the same.
0030H
Real number operation - invalid operation (non-nu-
meric)
No
Operation not executed.
0031H
Real number operation - exponent underflow
No
0.0
0032H
Real number operation - exponent overflow
No
Maximum value
0033H
Real number operation - division error (non-numer-
ic 0/0)
No
Operation not executed.
0034H
Real number storage - exponent underflow
No
Stores 0.0.
9