4-2 Basic Settings and Advanced Settings

4-35

IB-E

4

Set
ting V

a

rious

F

unct

ions

Laser emission stop input

The laser emission remains interrupted while the laser emission stop input is ON. The laser
radiation emission indicator on the sensor head and amplifier unit blink while the laser
emission is stopped.

" Amplifier control unit" (page 1-6)

Timing chart

*1

The internal measurement value (R.V.) changes to [-----] within max. 2 ms.

Minimum input time

ON time: 2 ms
OFF time: 2 ms

Set the method to switch the bank between the amplifier buttons and the external inputs.

"3-8 Bank Function (Registering Multiple Tolerance Setting Values)" (page 3-20)
" 10. External Input" (page 4-29)

Reference

While the laser emission, the R.V. is [-----].

"2 Display Screen and Output" (page A-9)

Max. 3 ms

*1

Max. 2 ms

Min. 2 ms

ON

OFF

Laser emission

stop input

Laser being transmitted

Laser being transmitted

Laser emission being stopped

11. Bank Switching Method

Setting

Description

Default

value

Button

The banks are switched by operating the amplifier
buttons.

External input

The banks are switched by turning ON/OFF the bank A
input or bank B input set in “11. External input”.