Operation when the power is turned on for the, First time -2, Ib-e – KEYENCE IB Series User Manual
Page 30: Ba sic o perat io ns, Make other settings as necessary, Analog output scaling" (page 4-27), Power on, Point, 5 initial reset (initialize)" (page 3-12)
3-2
IB-E
3
B
a
sic O
perat
io
ns
3-1
Operation when the Power is
Turned On for the First Time
When the amplifier is turned on for the first time after the sensor head is connected, the
initial setting display appears. Make the initial setting according to the following procedure
as this is necessary for both the main unit and the expansion units when units are added.
4
Carry out "3-3 Beam Axis Adjustment" (page 3-8) and "3-4 Reference
Light Registration (Gain Adjustment) and Adjust Function" (page 3-10).
Make other settings as necessary.
Point
Once the initial setting is completed, the initial setting display will
not appear when the power is turned on the second time or the after.
To change the initial setting, perform the initial reset.
"3-5 Initial Reset (Initialize)" (page 3-12)
1
Select the judgment output and check output polarity
with the / button, and press the [MODE] button.
[MODE] button
2
Press the / button to select the analog output
method and press the [MODE] button.
"9. Analog Output Scaling" (page 4-27)
[MODE] button
3
After the setting is complete, [end] blinks several
times on the sub display and changes to the main
screen.
Power ON
PRP
LASER
BANK
0
1
2
3
HI
LO
R.V.
ANALOG
HI SHIFT
ZERO SHIFT
TIMING
LO
ALIGNMENT
QWV
GO
HOLD CALC CHECK
Output polarity
Setting value
Description
npn
NPN output
pnp
PNP output
QHH
LASER
BANK
0
1
2
3
HI
LO
R.V.
ANALOG
HI SHIFT
ZERO SHIFT
TIMING
LO
ALIGNMENT
#P.)
GO
HOLD CALC CHECK
Analog output
Setting value
Description
off
Not output
0-5u
Analog output after the judgment value is converted to
the range from 0 to 5 V.
-5-5u
Analog output after the judgment value is converted to
±5 V.
1-5u
Analog output after the judgment value is converted to
the range from 1 to 5 V.
aMpr
Analog output after the judgment value is converted to
the range from 4 to 20 mA.
LASER
BANK
0
1
2
3
HI
LO
R.V.
ANALOG
HI
SHIFT
ZERO SHIFT
TIMING
LO
ALIGNMENT
GO
HOLD
CALC
CHECK
'PF