Chapter 7 Send Email
Logix5000 Controllers Common Procedures Programming Manual, publication
.
Enter the Ladder Logic
Ladder logic requires two MSG instructions. One MSG instruction configures
the mail server and needs to be executed only once. The second MSG instruction
triggers the email. Execute this email MSG instruction as often as needed.
The first rung configures the mail server. The second rung sends the email text.
Configure the MSG Instruction that Identifies the Mail Relay Server
To configure the MSG instruction that identifies the mail relay server, follow
these steps.
1. In the MSG instruction, click the Communication tab.
SetServer
- 1734-AENT EtherNet/IP Network Configuration User Manual 22-COMM-E EtherNet/IP Network Configuration User Manual 20-COMM-E EtherNet/IP Network Configuration User Manual 1794-AENT EtherNet/IP Network Configuration User Manual 1783-Etxx EtherNet/IP Network Configuration User Manual 1769-Lxxx EtherNet/IP Network Configuration User Manual 1756-Enxx EtherNet/IP Network Configuration User Manual