Control I/O Chapter 5
Rack-optimized
connection
For digital I/O modules, you can choose rack-optimized communication. A rack-optimized
connection consolidates connection usage between the controller and all the digital I/O modules
in the chassis (or DIN rail). Rather than having individual, direct connections for each I/O module,
there is one connection for the entire chassis (or DIN rail).
IMPORTANT
If you use different 1756 EtherNet/IP communication modules in a remote
chassis, such as a 1756-ENBT module and a 1756-EN2T module, do not use
a rack-optimized communication format to the remote chassis.
If you must use a rack-optimized communication format with a remote
1756 chassis, install the 1756-ENBT and 1756-EN2T modules in a separate
remote chassis.
Term
Definition
Rack-optimized
connection
- 1734-AENT EtherNet/IP Network Configuration User Manual 22-COMM-E EtherNet/IP Network Configuration User Manual 20-COMM-E EtherNet/IP Network Configuration User Manual 1794-AENT EtherNet/IP Network Configuration User Manual 1783-Etxx EtherNet/IP Network Configuration User Manual 1769-Lxxx EtherNet/IP Network Configuration User Manual 1756-Enxx EtherNet/IP Network Configuration User Manual