beautypg.com

Rockwell Automation 1734-AENTR EtherNet/IP Network Configuration User Manual User Manual

Page 114

background image

114

Rockwell Automation Publication ENET-UM001L-EN-P - March 2014

Chapter 9 Diagnostic Web Pages

Table 27 - Diagnostic Overview Web Page

Field

Specifies

Ethernet Link

Speed

Whether the Ethernet port is operating at 10 Mbps or 100 Mbps.

Duplex

Whether the Ethernet port is operating at half duplex or full duplex.

Autonegotiate Status

Whether the port speed and duplex mode were determined via autonegotiation or manual configuration.

System Resource Utilization

Number of times a page has been requested for which the user has insufficient privilege.

CPU

Current percent CPU utilization for the module.

CIP Connection Statistics

Current CIP MSG Connections

Current number of CIP connections for message.

Current CIP I/O Connections

Current number of CIP connections for I/O.

Conn Timeouts

Number of CIP connection timeouts.

TCP Connections (CIP)

Current TCP Connections

Current number of active TCP connections for CIP messaging.

I/O Packet / Second Statistics

Total

Total number of Class 1 UDP packets the module transmitted and received in the last one-second snapshot.
The Total is the sum of the Sent, Received, Inhibited, and Rejected numbers.

I/O Packet Counter Statistics

Missed

Cumulative number packets that were not received in order.
Each UDP packet has a sequence number and if a packet is missing (corrupted or dropped), the module will recognize this void
upon receipt of the next packet received.