Rockwell Automation 1734-AENTR EtherNet/IP Network Configuration User Manual User Manual
Page 80
![background image](/manuals/581404/80/background.png)
80
Rockwell Automation Publication ENET-UM001L-EN-P - March 2014
Chapter 6 Interlocking and Data Transfer between Controllers
Configure a MSG to an SLC 500 Controller
Configure a MSG to a PLC-5 Controller
3. Click the Communication tab.
4. In the Path field, type the communication path.
If the data is
And you want to
For this item
Type or choose
Integer
Read (receive) data
Message Type
SLC Typed Read
Source Element
Data table address in the SLC 500 controller (for example, N7:10)
Number of Elements
Number of integers to transfer
Destination Tag
First element of int_buffer
Write (send) data
Message Type
SLC Typed Write
Source Tag
First Element of int_buffer
Number of Elements
Number of integers to transfer
Destination Element
Data table address in the SLC 500 controller (for example, N7:10)
Floating-point (REAL)
Read (receive) data
Message Type
SLC Typed Read
Source Element
Data table address in the SLC 500 controller (for example, F8:0)
Number of Elements
Number of values to transfer
Destination Tag
First element of the tag (controller-scoped) in this controller for the data
Write (send) data
Message Type
SLC Typed Write
Source Tag
First element of the tag (controller-scoped) in this controller that contains the data
Number of Elements
Number of values to transfer
Destination Element
Data table address in the SLC 500 controller (for example, F8:0)
If the data is
And you want to
For this item
Type or choose
Integer
Read (receive) data
Message Type
PLC5 Typed Read
Source Element
Data table address in the PLC-5 controller (for example, N7:10)
Number of Elements
Number of integers to transfer
Destination Tag
First element of int_buffer
Write (send) data
Message Type
PLC5 Typed Write
Source Tag
First element of int_buffer
Number of Elements
Number of integers to transfer
Destination Element
Data Table address in the PLC-5 controller (for example, N7:10)
Floating-point (REAL)
Read (receive) data
Message Type
PLC5 Typed Read
Source Element
Data table address in the PLC-5 controller (for example, F8:0)
Number of Elements
Number of values to transfer
Destination Tag
First element of the tag (controller-scoped) in this controller for the data
Write (send) data
Message Type
PLC5 Typed Write
Source Tag
First element of the tag (controller-scoped) in this controller that contains the data
Number of Elements
Number of values to transfer
Destination Element
Data table address in the PLC-5 controller (for example, F8:0)
- 1734-AENT EtherNet/IP Network Configuration User Manual 22-COMM-E EtherNet/IP Network Configuration User Manual 20-COMM-E EtherNet/IP Network Configuration User Manual 1794-AENT EtherNet/IP Network Configuration User Manual 1783-Etxx EtherNet/IP Network Configuration User Manual 1769-Lxxx EtherNet/IP Network Configuration User Manual 1756-Enxx EtherNet/IP Network Configuration User Manual