Configure an EtherNet/IP Communication Module to Operate on the Network Chapter 3
EtherNet/IP communication modules are shipped with this configuration:
• BOOTP/DHCP enabled
• Rotary switches set to 999 - when applicable
This graphic shows the process used to set your module’s IP address.
Figure 2 - How Your Module’s IP Address is Set
If you need to reset your module’s settings to its factory default settings during
normal module operation,
Reset the Module IP Address to Factory Default Value
.
The tools are used in this sequence to set the network IP address:
1.
Set the Network IP Address with the Rotary Switches
2.
Set the Network IP Address with the BOOTP/DHCP Server
3.
Set the Network IP Address with RSLinx Software or the Studio 5000
Environment
Module Powerup
Module has an IP
address.
Switches set
from
001…254?
Yes
No
Is DHCP or
BOOTP
enabled?
Yes
No
Module requests
address from DHCP/
BOOTP server.
Module uses IP address
stored in nonvolatile
memory.
- 1734-AENT EtherNet/IP Network Configuration User Manual 22-COMM-E EtherNet/IP Network Configuration User Manual 20-COMM-E EtherNet/IP Network Configuration User Manual 1794-AENT EtherNet/IP Network Configuration User Manual 1783-Etxx EtherNet/IP Network Configuration User Manual 1769-Lxxx EtherNet/IP Network Configuration User Manual 1756-Enxx EtherNet/IP Network Configuration User Manual