Interlocking and Data Transfer between Controllers Chapter 6
Configure a MSG Instruction
To configure a MSG instruction, follow these steps.
1. Click
in the MSG box.
The Message Configuration dialog box appears.
2. Click the Configuration tab and specify the type of MSG instruction.
Configure a MSG to a Logix5000 Controller
...
If you want to
For this item
Type or choose
Read (receive) the data
Message Type
CIP Data Table Read
Source Element
First element of the tag that contains data in the other controller
Number of Elements
Number of elements to transfer
Destination Tag
First element of the tag (controller-scoped) in this controller for the data
Write (send) the data
Message Type
CIP Data Table Write
Source Tag
First element of the tag (controller-scoped) in this controller that contains the data
Number of Elements
Number of elements to transfer
Destination Element
First element of the tag for the data in the other controller
- 1734-AENT EtherNet/IP Network Configuration User Manual 22-COMM-E EtherNet/IP Network Configuration User Manual 20-COMM-E EtherNet/IP Network Configuration User Manual 1794-AENT EtherNet/IP Network Configuration User Manual 1783-Etxx EtherNet/IP Network Configuration User Manual 1769-Lxxx EtherNet/IP Network Configuration User Manual 1756-Enxx EtherNet/IP Network Configuration User Manual