Appendix M
Liquiline M CM42 Transmitter
Connect a Liquiline M CM42
Transmitter
Use a 2-wire connection to the HART input module.
Housing Grounding
You must connect the “Fixing plate” to the foundation ground with a separate
functional ground line (2.5 mm2 i14 AWG).
Stainless Steel Housing
You must connect the outer ground connection of the housing to the foundation
ground with a separate line (GN/YE) (
≥ 2.5 mm2 i14 AWG).
Item
Description
1
Fixing plate
2
2.5 mm2 (i14 AWG) functional ground
Item
Description
1
Outer ground connection
2
2.5 mm2 (i14 AWG) line (GN / YE)
This manual is related to the following products:
- 1734sc-IE2CH E+H Instruments via HART to PlantPAx User Manual 1769sc-IF4IH E+H Instruments via HART to PlantPAx User Manual 1794-IF8IH E+H Instruments via HART to PlantPAx User Manual 1756-IF16H E+H Instruments via HART to PlantPAx User Manual 1756-IF8IH E+H Instruments via HART to PlantPAx User Manual 1756-IF8H E+H Instruments via HART to PlantPAx User Manual