Test Valve Linearity with a Velocity Profile
1.
Select velocity vs. position control for the entire clamp close
operation by resetting the following bits to zero:
CPC03-B00 (B37/288)
CPC03-B02 (B37/290)
CPC03-B04 (B37/292)
2.
Download the CPC block to the QDC module.
Important: If downloading from your programming terminal, download
CPC by setting B21/6 (chapter 4).
3.
Jog your clamp to the full open position.
4.
Enable first clamp close by setting DYC02-B00 (B34/400) to 1. The
clamp should move from its start position through the first clamp
close and low pressure close profiles. If no motion, verify that:
- no overtravel alarms are set. The QDC module inhibits clamp
close if SYS07-B00 through -B05 are set
- no programming error codes exist in SYS61 and SYS62
5.
Upon completion of clamp close, observe the velocity reported for 1st
clamp close segment 2 CPS12 (N43:664). This velocity should be
relatively close to the setpoint you entered in CPC12 (N43:248). If
the observed velocity is not within 25% of the setpoint, verify that:
- the values from your flow rate curves are correct
- your calculations are correct
If the observed velocity CPS12 is still not within 25% of CPC12, your
flow valve is not linear over the desired range of operation. Correct as
follows:
If:
And Your Selected
Valve is:
Then change FCC48
(N43:44) as follows:
CPS12 was less than CPC12 Direct Acting
Increase in 5% steps
Reverse Acting
Decrease in 5% steps
CPS12 was more than
CPC12
Direct Acting
Decrease in 5% steps
Reverse Acting
Increase in 5% steps
To do this: change FCC48, download the FCC block, and repeat steps 3-5.
Repeat as necessary.
6.
Copy final FCC48 (N43:44) into SCC48 and TCC48 (N43:104 and
164), and download these changes to the QDC module.