CHAPTER 6: CONTROLLING THE OUTPUT

The 2800 includes a relay output that can be used to control a light,
siren, or other device. The output is a Form-C Normally Open/
Normally Closed mechanical relay and is rated for up to 120VAC
2A. A sample wiring diagram is shown below:

Figure 1: Relay output connected to alarm

The output can be programmed to operate in one of 7 automatic
modes or it can operate in manual mode (default). The 7

automatic

modes allow the output to automatically turn on and off based
on individual alarms or any alarm. In

manual

mode the output is

controlled via keypad command or remotely via touch-tone phone
(See Chapter 7)
. A description of each mode is shown below:

AUTOMATIC MODES

Mode 1

: Output on when zone 1 goes into alarm. Off when alarm

is acknowledged.

Mode 2

: Output on when zone 2 goes into alarm. Off when alarm

is acknowledged.

Mode 3

: Output on when zone 3 goes into alarm. Off when alarm

is acknowledged.

Mode 4

: Output on when zone 4 goes into alarm. Off when alarm

is acknowledged.

Mode 5

: Output on when zone 5 goes into alarm. Off when alarm

is acknowledged.