Sensaphone 2800 User Manual
Page 54
Sensaphone 2800 Manual
52
ZONE CALIBRATION
Due to tolerance variations or other factors, you may need to
program an offset to calibrate the sensor. The offset can range from
-15 to +15 for Zones configured as temperature, and -100 to +100
for Zones configured as 4–20mA. Setting a positive number will
add that number to the Zone reading. Setting a negative number will
subtract the programmed value from the Zone reading. For instance,
if a temperature sensor consistently read two degrees high, you
could use the calibration feature to adjust that temperature down
two degrees. To make a value negative, precede the value with the
[RINGS/TAD/*] Key.
To calibrate a Zone:
1. Press the SET key.
2. Press the CALIBRATE key.
The 2800 will say “Enter Zone Number.”
3. Press the corresponding Zone key (1–8).
The 2800 will say “Enter Number.”