Sensaphone 2800 User Manual
Page 41
Chapter 4: Zone Programming
39
3) Press the Wireless Sensor Zone Number (5-8). The 2800 will
respond with information for the selected sensor, or press 0 and
you will receive diagnostics for all sensors.
A sample report for sensor 5 is described below:
“Wireless sensor 5, temperature”
“The power is off ”
“The battery is OK”
“Signal strength is 35 percent”
“Error rate is 0.1 percent”
HARD-WIRED ZONE CONFIGURATION
The 2800 is compatible with normally open, normally closed,
2.8K thermistor (temperature), 10K thermistor (temperature),
and 4-20mA type sensors. All of the Zones are configured
simultaneously by keying in a simple key sequence after connecting
all of your sensors. Make sure all sensors are in their normal state.
All 4–20mA transducers should be powered on.
NOTE: New temperature sensors will default con-
figure to 2.8K. If you are connecting any 10K
sensors to the 2800, these
must be configured man-
ually. Any sensor that was previously configured as
either 2.8K or 10K will maintain proper thermistor
type. (See the Manual Configuration section)
To configure the Zone Types:
1. Press the SET key.