beautypg.com

Sensaphone 2800 User Manual

Page 170

background image

Sensaphone 2800 Manual

168

Phone Interface

Terminals for connection to a two-wire analog telephone line

Line seizure terminals for connecting extension telephone devices

LED Indicators: (4) Hard-Wired Zone Alarms, (4) Wireless Zone
Alarms, Sound, Power, Battery OK, Phone in Use, Output On, and
System On

Relay Output: 2A 120VAC/2A 24VDC—Programmable for
automatic or manual switching

Power Supply
Power Supply: 120VAC/9VDC 60Hz 10W wall plug-in transformer
Power Consumption: 5 Watts

Power Protection: Metal Oxide Varistor

Battery Backup: 6V 3.4 AH sealed gel cell, provides up to 16
hours of back-up time

Environmental
Operating Temperature: 32–122 deg F (0–50 deg C)

Operating Humidity: 0–90% RH non-condensing

Storage Temperature: 32–140 deg F

Physical
Dimensions: 12.1"h x 7.3"w x 4.5"d

Weight: 5 lbs.

Enclosures:

• Solid Door Enclosure: ABS Plastic, UL94V-0 Flammability rating,
NEMA Type 1, 2, 3, 3R, 4, 4X, 12 & 13, IEC529, IP66.

• Clear Door Enclosure: ABS/PC blended plastic, UL94-5VB