Page 42
Sensaphone 2800 Manual
40
2. Press the CONFIGURE key.
The 2800 will prompt, “Enter 0 for automatic configuration, enter
zone number for manual configuration.” If you press “0”, the 2800
will scan each Zone input and determine the input type.
The Zones are now considered normal. If a normally closed Zone
becomes open, an alarm will occur. If a normally open Zone
becomes closed, an alarm will occur.
MANUAL ZONE CONFIGURATION (Hard-wired zone only)
If you would like to program the Zone type (NO, NC, temperature,
4–20mA) without going through the automatic process that scans
all Zones, this command will allow you to configure a single Zone.
This command is useful if you have alarms on other channels and
cannot use the automatic configuration process, or if you wish to
configure the Zone type without actually connecting the sensor.
NOTE: You MUST use manual configuration for
any zone connecting to a 10K temperature sensor.
To configure the Zone Type:
1. Press the SET key.
2. Press the CONFIGURE key.
The 2800 will prompt, “Enter 0 for automatic configuration, enter
zone number for manual configuration.”