Temperature monitoring, Cause, Solution – Sensaphone 2800 User Manual

Page 160: Problem 4

background image

Sensaphone 2800 Manual

158

c) Temperature may require

calibration.

d) The unit is using the wrong

temperature scale (Fahrenheit vs.
Celsius).

After moving or placing the sensor
away from ambient heat sources, the
temperature may be calibrated to
offset inaccurate normal reading by
several degrees.
Refer to Chapter 4.

Verify temperature scale.
Refer to Chapter 4.

TEMPERATURE MONITORING

(continued)

Cause

a) The zone is configured for the

wrong type of thermistor (i.e., 2.8k
vs. 10k)

b) Temperature sensing may be

affected by a source of ambient
heat (ie., direct sunlight, or heat
duct proximity).

Solution

Manually configure the zone as
described in Chapter 4.

Try moving the sensor to a different
location.

Problem 4

Temperature reading is inaccurate.