Sensaphone 2800 User Manual
Page 39
Chapter 4: Zone Programming
37
The 2800 will say “Enter zero for automatic configura-
tion”, “Enter zone number for manual configuration”,
“Enter pound (#) for Channel configuration”
3. Press “0”, for automatic sensor configuration.
The 2800 will say the following:
Zone 1 Open/Closed/ Temperature, etc...
Zone 2 Open/Closed/ Temperature, etc...
Zone 3 Open/Closed/ Temperature, etc...
Zone 4 Open/Closed/ Temperature, etc...
Zone 5 Wireless sensor (serial number) humidity, signal
strength is 71 percent
Zone 6 Wireless sensor (serial number) temperature, signal
strength is 74 percent
Zone 7 Wireless sensor (serial number) power, signal
strength is 68 percent
Zone 8 Wireless sensor (serial number) water, signal
strength is 79 percent
Make sure each of your sensors has been recognized and assigned
to a zone number. The led next to the wireless sensor zone number
should be steady green.
NOTE: This procedure will not affect wireless sen-
sors that have already been configured.
Deleting Wireless Sensors
The Sensaphone 2800 monitors each wireless sensor to make sure
its is functioning properly. If a sensor is turned off, the 2800 will
notify you of a communication error for that particular channel. If
you need to permanently delete a sensor from the system, follow the
key sequence below:
1. Press the SENSOR ON/OFF key.