beautypg.com

Mounting, Electrical box installation, Surface installation – Sensaphone 2800 User Manual

Page 147

background image

Chapter 8: Sensors

145

MOUNTING

The wireless repeater can be mounted directly on a flat surface
or attached to a plastic single-gang electrical outlet box. Make
sure there is an electrical outlet nearby. Mount the device as high
as possible to provide for optimal wireless transmission. When
installed within a building where the wireless signal must travel
through several obstructions, the device should be located within
300’ of the Sensaphone 2800 and within 100’ of any sensors. If the
repeater has line-of-sight with the Sensaphone 2800, then it may be
located up to 4,000’ away.

Electrical box installation

Using the hex key remove the repeater cover by turning the two
hex screws located on the bottom of the sensor housing clockwise.
Carefully lift off the cover. Attach the sensor housing to the
electrical box using the appropriate screws.

Surface installation

Remove the repeater cover by turning the two hex screws on the
bottom of the sensor housing clockwise. Use a pencil to mark the
hole locations at the top and bottom of the housing. Remove the
device from the wall. Install the drywall anchors (if necessary) to
the wall. Attach the housing to the wall using #6 tapping screws.

+

+

+

Mounting

Screws

A1

A0

1
0