NORD Drivesystems BU0505 User Manual
Page 88
SK 54xE – Users Manual for Frequency Inverters
88
BU 0505 GB-1013
P211
Dynamic boost
(Dynamic boost)
S
P
0 ... 150 %
{ 100 }
The dynamic boost affects the torque generating current and is therefore a load-dependent
parameter. The factory 100% setting is also sufficient for typical applications.
Too high a value can lead to overcurrent in the FI. Under load therefore, the output voltage will be
raised too sharply. Too low a value will lead to insufficient torque.
Pos : 132 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P212 – Sc hlupf kompens ation @ 0\ mod_1327590275572_388. doc x @ 8140 @ @ 1
P212
Slip compensation
(Slip compensation)
S
P
0 ... 150 %
{ 100 }
The slip compensation increases the output frequency, dependent on load, to keep the
asynchronous motor speed approximately constant.
The factory setting of 100% is optimal when using DC asynchronous motors and correct motor data
has been set.
If several motors (different loads or outputs) are operated with one FI, the slip compensation P212
must be set to 0%. This rules out a negative influence. This is equally valid for synchronous motors
that do not have slip due to their design.
Pos : 133 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P213 – Verst. ISD-R egel ung @ 0\ mod_1327590323026_388.doc x @ 8163 @ @ 1
P213
ISD ctrl. loop gain
(Amplification of ISD control)
S
P
25 ... 400 %
{ 100 }
This parameter influences the control dynamics of the FI current vector control (ISD control). Higher
settings make the controller faster, lower settings slower.
Dependent on application type, this parameter can be altered, e.g. to avoid unstable operation.
Pos : 134 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P214 – Vorhalt Dr ehmoment @ 0\ mod_1327590368794_388. doc x @ 8186 @ @ 1
P214
Torque precontrol
(Torque precontrol)
S
P
-200 ... 200 %
{ 0 }
This function allows a value for the expected torque requirement to be set in the controller. This
function can be used in lifting applications for a better load transfer during start-up.
NOTE:
Motor torques (with rotation field right) are entered with a positive sign, generator
torques are entered with a negative sign. The reverse applies for the counter
clockwise rotation.
Pos : 135 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P215 – Boos t Vor halt @ 0\ mod_1327590415702_388. doc x @ 8209 @ @ 1
P215
Boost precontrol
(Boost precontrol)
S
P
0 ... 200 %
{ 0 }
Only advisable with linear characteristic curve (P211 = 0% and P212 = 0%).
For drives that require a high starting torque, this parameter provides an option for switching in an
additional current during the start phase. The application time is limited and can be selected at
parameter >Time boost precontrol< P216.
All current and torque current limits that may have been set (P112 and P536, P537) are deactivated
during the boost lead time.
NOTE:
With active ISD control (P211 and / or P212 ≠ 0%), parameterisation of P215 ≠ 0 results in incorrect
control.
Pos : 136 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P216 – Zeit Boost Vor hal t @ 0\ mod_1327590478846_388.doc x @ 8232 @ @ 1