5 parameters, P101 copy parameter set, P102 acceleration time – NORD Drivesystems BU0505 User Manual
Page 79: P103 braking time
5 Parameters
BU 0505 GB-1013
79
P101
Copy parameter set
(Copy parameter set)
S
0 ... 4
{ 0 }
After confirmation with the OK / ENTER key, a copy of the parameter set selected in P100
>Parameter set< is written to the parameter set dependent on the value selected here
0 = Do not copy
1 = Copy actual to P1: Copies the active parameter set to parameter set 1
2 = Copy actual to P2: Copies the active parameter set to parameter set 2
3 = Copy actual to P3: Copies the active parameter set to parameter set 3
4 = Copy actual to P4: Copies the active parameter set to parameter set 4
Pos : 105 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P100-P199Par ameter P102 – H oc hlaufz eit @ 0\ mod_1327574880847_388. doc x @ 7527 @ @ 1
P102
Acceleration time
(Acceleration time)
P
0 ... 320.00 sec
{ 2.00 }
{ 5.00 } above size 8
The acceleration time is the time corresponding to the linear frequency rise from 0Hz to the set
maximum frequency (P105). If an actual setpoint of <100% is being used, the acceleration time is
reduced linearly according to the setpoint set.
The acceleration time can be extended by certain circumstances, e.g. FI overload, setpoint lag,
smoothing, or if the current limit is reached.
NOTE:
Care must be taken that the parameter values are realistic. A setting of P102 = 0 is not
permissible for drive units!
Information on ramp gradient:
Ultimately, the moment of inertia of the rotor determines the possible ramp gradient.
If the ramp is too steep, the motor may "break down".
Extremely steep ramps (e.g.: 0 - 50Hz in < 0.1 s) should generally be avoided, as these may
cause damage to the frequency inverter.
Pos : 106 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P100-P199Par ameter P103 – Bremsz eit @ 0\ mod_1327574939362_388. doc x @ 7550 @ @ 1
P103
Braking time
(Deceleration time)
P
0 ... 320.00 sec
{ 2.00 }
{ 5.00 } above size 8
The braking time is the time corresponding to the linear frequency reduction from the set
maximum frequency (P105) to 0Hz (P105). If an actual setpoint <100% is being used, the
deceleration time reduces accordingly.
The braking time can be extended by certain circumstances, e.g. by the selected >Switch-off
mode< (P108) or >Ramp smoothing< (P106).
NOTE:
Care must be taken that the parameter values are realistic. A setting of P103 = 0 is not
permissible for drive units!
For information about ramp gradients: please refer to parameter (P102)