Basic parameters, P002 display factor, P003 supervisor-code – NORD Drivesystems BU0505 User Manual
Page 78: P100 parameter set
![background image](/manuals/372732/78/background.png)
SK 54xE – Users Manual for Frequency Inverters
78
BU 0505 GB-1013
P002
Display factor
(Display factor)
S
0.01 ... 999.99
{ 1.00 }
The selected operating value in parameter P001 >Select of display< is multiplied with the scaling
factor in P000 and displayed in >Operating parameter display<.
It is therefore possible to display system-specific operating such as e.g. the throughput quantity
Pos : 101 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P000-P099/ Paramet er P003 – Super visor-C ode @ 0\ mod_1327573882472_388. doc x @ 7432 @ @ 1
P003
Supervisor-Code
(Supervisor code)
0 ... 9999
{ 1 }
0 = The Supervisor parameters are not visible.
1 = All parameters are visible.
2 = Only the menu group 0 > Operating display< (P001 and P003) is visible.
3 = ... ... 9999, as for setting value 2.
Pos : 102 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ P1xx Basis paramet er @ 0\ mod_1327574618174_388. doc x @ 7458 @ 5 @ 1
Basic parameters
Parameter
{factory setting}
Setting value / Description / Note
Supervisor
Parameter
set
Pos : 103 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P100-P199Par ameter P100 – Par ameters atz @ 0\ mod_1327574757831_388. doc x @ 7481 @ @ 1
P100
Parameter set
(Parameter set)
S
0 ... 3
{ 0 }
Selection of the parameters sets to be parameterised. 4 parameter sets are available. All
parameter set-dependent parameters are identified by P.
The selection of the operating parameter set is performed via a digital input or the Bus control.
Switching can take place during operation (online).
Setting
Digital
inputfunction [8]
Digital
inputfunction [17]
LEDs
olBox
0 = Parameter set 1
LOW
LOW
1
2
1 = Parameter set 2
HIGH
LOW
2
1
2 = Parameter set 3
LOW
HIGH
1
2
3 = Parameter set 4
HIGH
HIGH
2
1
If enabled via the keyboard (SimpleBox, ControlBox, PotentiometerBox or ParameterBox), the
operating parameter set will match the settings in P100.