E013

13.0

Encoder error

No signal from encoder

Check 5V sensor if present.

Check supply voltage of encoder.

13.1

Speed slip error

"Speed slip error"

The slip speed error limit was reached.

Increase setting in P327.

13.2

Shut-down monitoring

The slip error monitoring has triggered; the motor could not
follow the setpoint.

Check motor data P201-P209! (Important for the
current controller)

Check motor circuit.

In servo mode, check the encoder setting P300 and
check the following

Increase setting value for torque limit in P112.

Increase setting value for current limit in P536.

Check deceleration time P103 and extend if
necessary

13.5

Reserved

Error message for POSICON

à see supplementary

instructions

13.6

Reserved

Error message for POSICON

à see supplementary

instructions

Pos : 412 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E014 "res er viert" [ SK 180E ... SK 5xxE] @ 2\ mod_1347454273854_388.doc x @ 46776 @ @ 1

E014

---

Reserved

Error message for POSICON

à see supplementary

instructions

Pos : 413 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E015 [ SK 180E ... SK 5xxE] @ 2\ mod_1347454278051_388.doc x @ 46801 @ @ 1

E015

---

Reserved

Pos : 414 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E016 [ SK 135E ... SK 5xxE] @ 2\ mod_1347454280625_388.doc x @ 46826 @ @ 1

E016

16.0

Motor phase error

A motor phase is not connected.

Check P539

Check motor connection

16.1

Magnetisation current
monitoring

"Magnetisation current
monitoring"

Required exciting current not achieved at moment of switch-
on.

Check P539

• Check motor connection

Pos : 415 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E018 "res er viert" [ SK 2xxE/F ehler E018 "reser vi ert" [ SK 2xxE/SK 5xxE] @ 2\ mod_1347454282777_388.doc x @ 46851 @ @ 1

E018

18.0

Reserved

Error message for "Safe Pulse Block"

à see supplementary

instructions

Pos : 416 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E019 [ SK 180E/ SK 2xxE/Fehler E019 [SK 180E/SK 2xxE/ SK 5xxE] @ 2\ mod_1347454285788_388. doc x @ 46876 @ @ 1

E019

19.0

Parameter identification

"Parameter identification"

Automatic identification of the connected motor was
unsuccessful

• Check motor connection

Check pre-set motor data (P201 ... P209)

19.1

Star / Delta circuit incorrect

"Star / delta motor circuit
incorrect

Pos : 417 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E020 /F ehl er E020 / E021 [ SK 135E .. . SK 5xxE] @ 2\ mod_1347454288768_388. doc x @ 46901 @ @ 1

E020

E021

20.0

Reserved

System error in program execution, triggered by EMC
interference.

Observe wiring guidelines

Use additional external mains filter.

Earth the FI very well.

20.1

Watchdog

20.2

Stack Overflow

20.3

Stack underflow

20.4

Undefined Opcode

20.5

Protected Instruct.

„Protected Instruction“

20.6

Illegal Word Access

20.7

Illegal Inst.

Access

“Illegal Instruction Access”