6 operating status messages – NORD Drivesystems BU0505 User Manual
Page 153
6 Operating status messages
BU 0505 GB-1013
153
E013
13.0
Encoder error
No signal from encoder
•
Check 5V sensor if present.
•
Check supply voltage of encoder.
13.1
Speed slip error
"Speed slip error"
The slip speed error limit was reached.
•
Increase setting in P327.
13.2
Shut-down monitoring
The slip error monitoring has triggered; the motor could not
follow the setpoint.
•
Check motor data P201-P209! (Important for the
current controller)
•
Check motor circuit.
•
In servo mode, check the encoder setting P300 and
check the following
•
Increase setting value for torque limit in P112.
•
Increase setting value for current limit in P536.
•
Check deceleration time P103 and extend if
necessary
13.5
Reserved
Error message for POSICON
à see supplementary
instructions
13.6
Reserved
Error message for POSICON
à see supplementary
instructions
Pos : 412 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E014 "res er viert" [ SK 180E ... SK 5xxE] @ 2\ mod_1347454273854_388.doc x @ 46776 @ @ 1
E014
---
Reserved
Error message for POSICON
à see supplementary
instructions
Pos : 413 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E015 [ SK 180E ... SK 5xxE] @ 2\ mod_1347454278051_388.doc x @ 46801 @ @ 1
E015
---
Reserved
Pos : 414 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E016 [ SK 135E ... SK 5xxE] @ 2\ mod_1347454280625_388.doc x @ 46826 @ @ 1
E016
16.0
Motor phase error
A motor phase is not connected.
•
Check P539
•
Check motor connection
16.1
Magnetisation current
monitoring
"Magnetisation current
monitoring"
Required exciting current not achieved at moment of switch-
on.
•
Check P539
• Check motor connection
Pos : 415 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E018 "res er viert" [ SK 2xxE/F ehler E018 "reser vi ert" [ SK 2xxE/SK 5xxE] @ 2\ mod_1347454282777_388.doc x @ 46851 @ @ 1
E018
18.0
Reserved
Error message for "Safe Pulse Block"
à see supplementary
instructions
Pos : 416 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E019 [ SK 180E/ SK 2xxE/Fehler E019 [SK 180E/SK 2xxE/ SK 5xxE] @ 2\ mod_1347454285788_388. doc x @ 46876 @ @ 1
E019
19.0
Parameter identification
"Parameter identification"
Automatic identification of the connected motor was
unsuccessful
• Check motor connection
•
Check pre-set motor data (P201 ... P209)
19.1
Star / Delta circuit incorrect
"Star / delta motor circuit
incorrect
Pos : 417 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E020 /F ehl er E020 / E021 [ SK 135E .. . SK 5xxE] @ 2\ mod_1347454288768_388. doc x @ 46901 @ @ 1
E020
E021
20.0
Reserved
System error in program execution, triggered by EMC
interference.
•
Observe wiring guidelines
•
Use additional external mains filter.
•
Earth the FI very well.
20.1
Watchdog
20.2
Stack Overflow
20.3
Stack underflow
20.4
Undefined Opcode
20.5
Protected Instruct.
„Protected Instruction“
20.6
Illegal Word Access
20.7
Illegal Inst.
Access
“Illegal Instruction Access”