5 Parameters

BU 0505 GB-1013

87

P205

Nominal power

(Nominal motor power output)

P

0.00 ... 250.00 kW

{

***

}

The motor nominal power controls the motor set via P200.

Pos : 126 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P206 – M ot or c os phi @ 0\ mod_1327588784877_388. doc x @ 7999 @ @ 1

P206

Cos phi

(Motor cos

j

)

S

P

0.50 ... 0.90

{

***

}

The motor cos

j is a decisive parameter for the current vector control.

Pos : 127 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P207 – M ot orsc halt ung @ 0\ mod_1327589654065_388. doc x @ 8022 @ @ 1

P207

Star Delta con.

(Star Delta connection)

S

P

0 ... 1

{

***

}

0 = Star

1 = Delta

The motor circuit is decisive for stator resistance measurement (P220) and therefore for current
vector control.

Pos : 128 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P208 – St at or widerst and @ 0\ mod_1327589723457_388. doc x @ 8045 @ @ 1

P208

Stator resistance

(Stator resistance)

S

P

0.00 ... 300.00 W

{

***

}

Motor stator resistance

Þ resistance of a phase winding with a DC motor.

Has a direct influence on the current control of the FI. Too high a value will lead to a possible
overcurrent; too low a value to a motor torque that is too low.

The parameter P220 can be used for simple measurement. Parameter P208 can be used for
manual setting or as information about the result of an automatic measurement.

NOTE:

For optimum functioning of the current vector control, the stator resistance must be automatically
measured by the FI.

Pos : 129 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P209 – Leerl aufstrom @ 0\ mod_1327589796537_388. doc x @ 8068 @ @ 1

P209

No load current

(No load current)

S

P

0.1 ... 1000.0 A

{

***

}

This value is always calculated automatically from the motor data if there is a change in the
parameter >cos

j< P206 and the parameter >Nominal current< P203.

NOTE:

If the value is to be entered directly, then it must be set as the last motor data. This is

the only way to ensure that the value will not be overwritten.

Pos : 130 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P210 – St atisc her Boost @ 0\ mod_1327590156790_388. doc x @ 8094 @ @ 1

P210

Static boost

(Static boost)

S

P

0 ... 400 %

{ 100 }

The static boost affects the current that generates the magnetic field. This is equivalent to the no
load current of the respective motor and is therefore load-independent. The no load current is
calculated using the motor data. The factory setting of 100% is sufficient for normal applications.

Pos : 131 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P211 – D ynamisc her Boos t @ 0\ mod_1327590224915_388.doc x @ 8117 @ @ 1

*** These settings are dependent on the nominal power of the FI or the selection in parameter P200.