2 assembly and installation – NORD Drivesystems BU0505 User Manual
Page 51
2 Assembly and installation
BU 0505 GB-1013
51
Relevance
SK 540E
SK 545E
SK 510E
SK 511E
SK 515E
SK 520E
SK 530E
SK 535E
√
Terminals X5:
21
22
23
24
25 / 39
41 / 38
44*
40
* Terminal 44:
up to Size 4: VI
Size 5 and
above: VO
DIN1
DIN2
DIN3
DIN4
DIN5 / TF-
VO 5V / TF+
V…24V
GND/0V
Name
Terminal Function
[factory setting]
Data
Description / wiring suggestion
Parameter
21
Digital input 1
[ON right]
7.5...30V, R
i
=6.1k
W
Not suitable for thermistor
evaluation.
HTL encoders can only be
connected to DIN2 and
DIN4
Limiting frequencies:
max.
10 kHz
min.
15 Hz
Each digital input has a reaction time of
≤ 5ms.
Sizes 1 to 4
21
22
23
24
39
38
44
40
motor - PTC
GND / 0V
18 … 30V
Above size 5
21
22
23
24
25
41
44
40
GND / 0V
18 … 30V
P420 [-01]
22
Digital input 2
[ON left]
P420 [-02]
23
Digital input 3
[parameter set bit0]
P420 [-03]
24
Digital input 4
[Fixed frequency 1,
P429]
P420 [-04]
25
Digital input 5
[no function]
Available: above size 5
P420 [-05]
39
Thermistor input -
available: Size 1 - 4
potential isolated
thermistor input, which
cannot be disabled, for
monitoring the motor
temperature with a PTC
38
Thermistor input +
41
5V output power
supply
Available: above size 5
5V
± 10%
44
Size 1 to Size 4
VI 24V supply
voltage input
18…30V
at least 800mA (input)
Voltage supply for the FI control unit. Is
essential for the function of the
frequency inverter.
Size 5 and above
VO 24V supply
voltage output
24V ± 25%
max. 200mA (output)
Supply voltage provided by the
frequency inverter for connection to the
digital inputs or the supply of a 10-30V
encoder.
The 24V control voltage is generated by
the FI, however it can alternatively be
supplied via the terminals X12:44/40
(size 8 and above: X15:44/40). Supply
via terminal X5:44 is not possible.
40
Reference potential
for digital signals
0V digital
Reference potential
Pos : 63 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 10. 5 Elektrischer Ansc hluss St euert eil- Klemmenbl oc k X6 – Enc oder [SK 54xE] @ 2\ mod_1355475336807_388. doc x @ 52162 @ 5 @ 1