beautypg.com

NORD Drivesystems BU0505 User Manual

Page 123

background image

5 Parameters

BU 0505 GB-1013

123

P515

[-01]

...

[-03]

CAN address

(CAN address)

0 ... 255

{ all 50 }

Setting of the basic CANbus address for CAN and CANopen. With the use of the CANopen
technology unit, settings from this parameter are only valid if the BAUD rotary coding switch on
the technology unit has been set to PGM.

Information

Data takeover

The baud rate is only read after a Power On, a Reset Node message or a Power On of the
24V bus supply.

From software version 1.6 and above, this can be set in three levels:

[-01] = Slave address, Receipt address for CAN and CANopen (as before)

[-02] = Broadcast slave address, Broadcast – receipt address for CANopen (Slave)

[-03] = Master address, Broadcast – Transmission address for CANopen (Master)

Pos : 275 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P516 – Ausbl endfr equenz 1 @ 0\ mod_1328092606664_388.doc x @ 11249 @ @ 1

P516

Skip frequency 1

(Skip frequency 1)

S

P

0.0 ... 400.0 Hz

{ 0.0 }

The output frequency around the frequency value (P517) set here is not shown.

This range is transmitted with the set brake and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.

0 = Skip frequency inactive

Pos : 276 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P517 – Ausbl endber eic h 1 @ 0\ mod_1328092662665_388. doc x @ 11272 @ @ 1

P517

Skip freq. area 1

(Skip frequency area 1)

S

P

0.0 ... 50.0 Hz

{ 2.0 }

Skip range for the >Skip frequency 1< P516. This frequency value is added and subtracted from
the skip frequency.

Skip frequency range 1: P516 - P517 ... P516 + P517

Pos : 277 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P518 – Ausbl endfr equenz 2 @ 0\ mod_1328092706493_388.doc x @ 11295 @ @ 1

P518

Skip frequency 2

(Skip frequency 2)

S

P

0.0 ... 400.0 Hz

{ 0.0 }

The output frequency around the set frequency value (P519) is skipped.

This range is transmitted with the set brake and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.

0 = Skip frequency inactive

Pos : 278 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P519 – Ausbl endber eic h 2 @ 0\ mod_1328092748353_388. doc x @ 11318 @ @ 1

P519

Skip freq. area 2

(Skip frequency area 2)

S

P

0.0 ... 50.0 Hz

{ 2.0 }

Skip range for the >Skip frequency 2< P518. This frequency value is added and subtracted from
the skip frequency.

Skip frequency range 2: P518 - P519 ... P518 + P519

Pos : 279 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P520 – Fangschalt ung @ 0\ mod_1328092790587_388. doc x @ 11341 @ @ 1